A/D Conversion Enable/Disable (Address "0")

A/D Conversion Enable/Disable (Address "0")

Address

Function

R/W

Hex

Dec

0H

0

A/D Conversion Enable/Disable

R

Buffer offset "0" stores the information whether to perform A/D conversion in each channel.
To validate the A/D Conversion Enable/Disable settings, Y02 should be turned ON then OFF.

 

The default value of all channel is "0".

Bits

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

CH16

CH15

CH14

CH13

CH12

CH11

CH10

CH9

CH8

CH7

CH6

CH5

CH4

CH3

CH2

CH1

1 : Enable, 0 : Disable

In case of 8-channel module, B8~B15(CH.9 ~ CH.16) are not used.

 

If the channel is set to "0" (Disable), the channel does not perform A/D Conversion.
(Example) If channel 2, 4, 6, 7 uses A/D Conversion, the value H006A (Decimal: 106) is stored in the buffer offset "0".

Bits

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

CH16

CH15

CH14

CH13

CH12

CH11

CH10

CH9

CH8

CH7

CH6

CH5

CH4

CH3

CH2

CH1

0

0

0

0

0

0

0

0

0

1

1

0

1

0

1

0

0

0

6

A