TC converter modules are used to receive inputs from thermocouples (K, J, E, T, B ,R,S), to measure their temperatures and to convert the temperatures to signed 16-bit binary digital value.
Seven kinds of thermocouple can be directly connected to a TC converter module to convert temperature(oC) data to the digital values used in PLCs.
Features :
The temperatures converted in the state that 7 kinds(K, J, E, T, R, S, B) of thermocouple are connected to a TC module can be indicated in Centigrade or Fahrenheit(oC, oF) and the temperature values can be processed as digital values up to the first decimal place.
Converted temperature data are converted to 16-bit binary data, which can be processed as digital values. The min. value and the max. value of each thermocouple are converted to 0 and 16000(-8000~8000).
Temperatures are expressed up to min. value of -50oC and max. value of +50oC and digital values are expressed in the range from –192 to 16191(- 8192~8191).
If a minimum temperature value and a maximum temperature value are set up, the minimum value will be converted to 0(-8000) and the maximum value to 16000(8000).
The breaking of thermocouples and cables and the excess of measuring range are detected by channels..
It is available to connect 4 thermocouples with one module.
The number of the modules used on one base is not limited.