High Alarm set Value (Address "113"-"128")

High Alarm Set Value (Address "113"-"128")

Address

Function

R/W

Hex

Dec

71H

113

CH.1 High Alarm Set Value

R/W

72H

114

CH.2 High Alarm Set Value

R/W

73H

115

CH.3 High Alarm Set Value

R/W

74H

116

CH.4 High Alarm Set Value

R/W

75H

117

CH.5 High Alarm Set Value

R/W

76H

118

CH.6 High Alarm Set Value

R/W

77H

119

CH.7 High Alarm Set Value

R/W

78H

120

CH.8 High Alarm Set Value

R/W

79H

121

CH.9 High Alarm Set Value

R/W

7AH

122

CH.10 High Alarm Set Value

R/W

7BH

123

CH.11 High Alarm Set Value

R/W

7CH

124

CH.12 High Alarm Set Value

R/W

7DH

125

CH.13 High Alarm Set Value

R/W

7EH

126

CH.14 High Alarm Set Value

R/W

7FH

127

CH.15 High Alarm Set Value

R/W

80H

128

CH.16 High Alarm Set Value

R/W

In case of 8-channel module, address 121~128 are not used.

To use High Alarm by comparing A/D conversion value, the High Alarm Value is assigned based on the Present Value (Offset 11~18).
If the converted value exceeds the High Alarm Value, the corresponding contact and buffer is set to "Alert"

 

Configurable range is as shown below.

Output Format

Range

Unsigned Value

0 ~ 16,000

Signed Value

-8,000 ~ 8,000

Regular Value

4 ~ 20 mA

4,000 ~ 20,000

0 ~ 20 mA

0 ~ 20,000

1 ~ 5 V

1,000 ~ 5,000

0 ~ 5 V

0 ~ 5,000

-10 ~ 10 V

-10,000 ~ 10,000

0 ~ 10 V

0 ~ 10,000

Percentage

0 ~ 10,000

To disable High/Low Alarm Value feature, set both bound values to "0".