Buffer Memory - A/D Converters(AD08VI/AD16VI)

 

Address

Function

Note

R / W

Hex

Dec

0H

0

A/D Enable / Disable

 

R/W

1H

1

Flags : AD Converting Completed

 

R

2H

2

A/D Conversion Value Output Format (ch1 .. ch4)

 

R/W

3H

3

A/D Conversion Value Output Format (ch5 .. ch8)

 

R/W

4H

4

A/D Conversion Value Output Format (ch9 .. ch12)

Not used in AD08VI

R/W

5H

5

A/D Conversion Value Output Format (ch13 .. ch16)

R/W

6H

6

Flags : Maintain last normal measured value

 

R/W

7H

7

Key Code for calibration (Prohibited for users)

 

R/W

8H

8

Key Code for calibration (Prohibited for users)

 

R/W

9H

9

Flags : High Alarm Status

 

R

AH

10

Flags : Low Alarm Status

 

R

BH

11

Ch1 Converted Value

 

R

CH

12

Ch2 Converted Value

 

R

DH

13

Ch3 Converted Value

 

R

EH

14

Ch4 Converted Value

 

R

FH

15

Ch5 Converted Value

 

R

10H

16

Ch6 Converted Value

 

R

11H

17

Ch7 Converted Value

 

R

12H

18

Ch8 Converted Value

 

R

13H

19

Ch9 Converted Value

Not used in AD08VI

R

14H

20

Ch10 Converted Value

R

15H

21

Ch11 Converted Value

R

16H

22

Ch12 Converted Value

R

17H

23

Ch13 Converted Value

R

18H

24

Ch14 Converted Value

R

19H

25

Ch15 Converted Value

R

1AH

26

Ch16 Converted Value

R

1BH

27

CH.1(Low), CH.2(High) Input Sig. Range

 

R/W

1CH

28

CH.3(Low), CH.4(High) Input Sig. Range

 

R/W

1DH

29

CH.5(Low), CH.6(High) Input Sig. Range

 

R/W

1EH

30

CH.7(Low), CH.8(High) Input Sig. Range

 

R/W

1FH

31

Ch9(Low), Ch10(High) Input Sig. Range

Not used in AD08VI

R/W

20H

32

Ch11(Low), Ch12(High) Input Sig. Range

R/W

21H

33

Ch13(Low), Ch14(High) Input Sig. Range

R/W

22H

34

Ch15(Low), Ch16(High) Input Sig. Range

R/W

23H

35

CH.1(Low), CH.2(High) Digital Filter Const. (0~99%)

 

R/W

24H

36

CH.3(Low), CH.4(High) Digital Filter Const. (0~99%)

 

R/W

25H

37

CH.5(Low), CH.6(High) Digital Filter Const. (0~99%)

 

R/W

26H

38

CH.7(Low), CH.8(High) Digital Filter Const. (0~99%)

 

R/W

27H

39

Ch9(Low), Ch10(High) Digital Filter Const. (0~99%)

Not used in AD08VI

R/W

28H

40

Ch11(Low), Ch12(High) Digital Filter Const. (0~99%)

R/W

29H

41

Ch13(Low), Ch14(High) Digital Filter Const. (0~99%)

R/W

2AH

42

Ch15(Low), Ch16(High) Digital Filter Const. (0~99%)

R/W

2BH

43

CH.1 Average WIN size

 

R/W

2CH

44

CH.2 Average WIN size

 

R/W

2DH

45

CH.3 Average WIN size

 

R/W

2EH

46

CH.4 Average WIN size

 

R/W

2FH

47

CH.5 Average WIN size

 

R/W

30H

48

CH.6 Average WIN size

 

R/W

31H

49

CH.7 Average WIN size

 

R/W

32H

50

CH.8 Average WIN size

 

R/W

33H

51

Ch9 Average WIN size

Not used in AD08VI

R/W

34H

52

Ch10 Average WIN size

R/W

35H

53

Ch11 Average WIN size

R/W

36H

54

Ch12 Average WIN size

R/W

37H

55

Ch13 Average WIN size

R/W

38H

56

Ch14 Average WIN size

R/W

39H

57

Ch15 Average WIN size

R/W

3AH

58

Ch16 Average WIN size

R/W

3BH

59

Reserved

 

-

3CH

60

BSN Key Code (Prohibited for users)

 

-

3DH

61

F/W Third Version

 

R

3EH

62

Error Code

 

R

3FH

63

OS Version

 

R

40H

64

CH.1 Measured Value (Raw)

 

R

41H

65

CH.2 Measured Value (Raw)

 

R

42H

66

CH.3 Measured Value (Raw)

 

R

43H

67

CH.4 Measured Value (Raw)

 

R

44H

68

CH.5 Measured Value (Raw)

 

R

45H

69

CH.6 Measured Value (Raw)

 

R

46H

70

CH.7 Measured Value (Raw)

 

R

47H

71

CH.8 Measured Value (Raw)

 

R

48H

72

CH.9 Measured Value (Raw)

Not used in AD08VI

R

49H

73

CH.10 Measured Value (Raw)

R

4AH

74

CH.11 Measured Value (Raw)

R

4BH

75

CH.12 Measured Value (Raw)

R

4CH

76

CH.13 Measured Value (Raw)

R

4DH

77

CH.14 Measured Value (Raw)

R

4EH

78

CH.15 Measured Value (Raw)

R

4FH

79

CH.16 Measured Value (Raw)

R

50H

80

Ch1 Minimum Value

 

R

51H

81

Ch2 Minimum Value

 

R

52H

82

Ch3 Minimum Value

 

R

53H

83

Ch4 Minimum Value

 

R

54H

84

Ch5 Minimum Value

 

R

55H

85

Ch6 Minimum Value

 

R

56H

86

Ch7 Minimum Value

 

R

57H

87

Ch8 Minimum Value

 

R

58H

88

Ch9 Minimum Value

Not used in AD08VI

R

59H

89

Ch10 Minimum Value

R

5AH

90

Ch11 Minimum Value

R

5BH

91

Ch12 Minimum Value

R

5CH

92

Ch13 Minimum Value

R

5DH

93

Ch14 Minimum Value

R

5EH

94

Ch15 Minimum Value

R

5FH

95

Ch16 Minimum Value

R

60H

96

Ch1 Maximum Value

 

R

61H

97

Ch2 Maximum Value

 

R

62H

98

Ch3 Maximum Value

 

R

63H

99

Ch4 Maximum Value

 

R

64H

100

Ch5 Maximum Value

 

R

65H

101

Ch6 Maximum Value

 

R

66H

102

Ch7 Maximum Value

 

R

67H

103

Ch8 Maximum Value

 

R

68H

104

Ch9 Maximum Value

Not used in AD08VI

R

69H

105

Ch10 Maximum Value

R

6AH

106

Ch11 Maximum Value

R

6BH

107

Ch12 Maximum Value

R

6CH

108

Ch13 Maximum Value

R

6DH

109

Ch14 Maximum Value

R

6EH

110

Ch15 Maximum Value

R

6FH

111

Ch16 Maximum Value

R

70H

112

Reserved

 

-

71H

113

CH.1 High Alarm Set Value

 

R/W

72H

114

CH.2 High Alarm Set Value

 

R/W

73H

115

CH.3 High Alarm Set Value

 

R/W

74H

116

CH.4 High Alarm Set Value

 

R/W

75H

117

CH.5 High Alarm Set Value

 

R/W

76H

118

CH.6 High Alarm Set Value

 

R/W

77H

119

CH.7 High Alarm Set Value

 

R/W

78H

120

CH.8 High Alarm Set Value

 

R/W

79H

121

Ch9 High Alarm Set Value

Not used in AD08VI

R/W

7AH

122

Ch10 High Alarm Set Value

R/W

7BH

123

Ch11 High Alarm Set Value

R/W

7CH

124

Ch12 High Alarm Set Value

R/W

7DH

125

Ch13 High Alarm Set Value

R/W

7EH

126

Ch14 High Alarm Set Value

R/W

7FH

127

Ch15 High Alarm Set Value

R/W

80H

128

Ch16 High Alarm Set Value

R/W

81H

129

CH.1 Low Alarm Set Value

 

R/W

82H

130

CH.2 Low Alarm Set Value

 

R/W

83H

131

CH.3 Low Alarm Set Value

 

R/W

84H

132

CH.4 Low Alarm Set Value

 

R/W

85H

133

CH.5 Low Alarm Set Value

 

R/W

86H

134

CH.6 Low Alarm Set Value

 

R/W

87H

135

CH.7 Low Alarm Set Value

 

R/W

88H

136

CH.8 Low Alarm Set Value

 

R/W

89H

137

Ch9 Low Alarm Set Value

Not used in AD08VI

R/W

8AH

138

Ch10 Low Alarm Set Value

R/W

8BH

139

Ch11 Low Alarm Set Value

R/W

8CH

140

Ch12 Low Alarm Set Value

R/W

8DH

141

Ch13 Low Alarm Set Value

R/W

8EH

142

Ch14 Low Alarm Set Value

R/W

8FH

143

Ch15 Low Alarm Set Value

R/W

90H

144

Ch16 Low Alarm Set Value

R/W

91H

145

PCB Production year (Prohibited for users)

 

R/W

92H

146

PCB Production Month/Date (Prohibited for users)

 

R/W

93H

147

Serial No. 1 (Prohibited for users)

 

R/W

94H

148

Serial No. 2 (Prohibited for users))

 

R/W

The use of buffer memory of AD08VI is same as AD16VI. Channels 9 to 16 are not used in AD08VI.
Converted Value : The value which is converted from the measured value (Raw) within the digital conversion range.
Minimum Value : Minimum value of the Converted Value.
Maximum Value : Maximum value of the Converted Value.
Measured Value (Raw) : The value which is measured in mA or V unit.
The AD module is equipped with shared memories inside called ‘buffer memory’. This buffer memory stores converted values and parameter values.
By using FROM instruction, it is possible to transfer the stored values in buffer memory to CPU memory, and utilize them in the scan program.
By using TO instruction, it is possible to store the parameter values in the buffer memory.
The size of each data is 2 bytes.