D/A Converters

D/A Modules are used to convert signed 16-bit binary digital values to analog signals (Direct voltage or direct current).

Features :
DA16I is a 16-channel current (4~20mA) output DA module.
DA08I is an 8-channel current (4~20mA) output DA module.
DA04I is a 4-channel current (4~20mA) output DA module.

DA16V is a 16-channel current (-10~10V) output DA module.
DA08V is an 8-channel voltage (-10~10V) output DA module.
DA04V is a 4-channel voltage (-10~10V) output DA module.

As the resolution for digital values is selected as 1/16000, high-resolution analog values will be gotten

DA converter modules are used to convert the digital values for signed 16-bit binary data (Data: 14 bits) set up in a CPU to analog signals (Voltage or current). The digital values in the range from 0 to 16000((-8000~8000) are converted to the analog values in the range from 4 to 20mA(-10~10V).

If you use the CICON to set up hold or clear, a DA output value will be outputted as offset value(4mA,-10V) or a current DA output value will be kept in case that a PLC is switched from RUN mode to STOP mode or an error occurs in a CPU.

The channel disabled to convert outputs offset value(4mA,-10V).

The number of modules on one base is not limited.
(But, they can be used within the range satisfying the capacity of a power module.)