Enabling / Disabling to A/D Convert (Address "0")
Buffer Memory Address "0"
This is used to set up whether enabling or disabling to A/D-convert by the channels.
To make it available to set up enabling/disabling to A/D-convert, requesting to set up operation condition (Y02) is to be set and reset.
Default value is set up as disabling A/D conversion.
As a set value is stored in EEPROM, the A/D module is operated as previously set value even though the power is on and off.
The data from b4 to b15 of AD04VI and the data from b8 to b15 of AD08I and ADO8V are fixed as "0".
Example :
In case that the channels for A/D conversion are 2,4,6,8, 00AAH(170) is to be written to Buffer Memory Address "0" and requesting to set up operation condition (Y02) is to be set and reset.