Enabling / Disabling to A/D Convert (Address "0")

Buffer Memory Address "0"

This is used to set up whether enabling or disabling to A/D-convert by the channels.
To make it available to set up enabling/disabling to A/D-convert, requesting to set up operation condition (Y02) is to be set and reset.
Default value is set up as disabling A/D conversion.
As a set value is stored in EEPROM, the A/D module is operated as previously set value even though the power is on and off.

 

image-20240325-040126.png

The data from b4 to b15 of AD04VI and the data from b8 to b15 of AD08I and ADO8V are fixed as "0".

 

Example :
In case that the channels for A/D conversion are 2,4,6,8, 00AAH(170) is to be written to Buffer Memory Address "0" and requesting to set up operation condition (Y02) is to be set and reset.

 