Low Alarm Set Value (Address "129"-"144")

Low Alarm Set Value (Address "129"-"144")

Address

Function

R/W

Hex

Dec

81H

129

CH.1 Low Alarm Set Value

R/W

82H

130

CH.2 Low Alarm Set Value

R/W

83H

131

CH.3 Low Alarm Set Value

R/W

84H

132

CH.4 Low Alarm Set Value

R/W

85H

133

CH.5 Low Alarm Set Value

R/W

86H

134

CH.6 Low Alarm Set Value

R/W

87H

135

CH.7 Low Alarm Set Value

R/W

88H

136

CH.8 Low Alarm Set Value

R/W

89H

137

CH.9 Low Alarm Set Value

R/W

8AH

138

CH.10 Low Alarm Set Value

R/W

8BH

139

CH.11 Low Alarm Set Value

R/W

8CH

140

CH.12 Low Alarm Set Value

R/W

8DH

141

CH.13 Low Alarm Set Value

R/W

8EH

142

CH.14 Low Alarm Set Value

R/W

8FH

143

CH.15 Low Alarm Set Value

R/W

90H

144

CH.16 Low Alarm Set Value

R/W

In case of 8-channel module, address 137~144 are not used.

To use Low Alarm by comparing A/D conversion value, the Low Alarm Value is assigned based on the Present Value (Offset 11~18).
If the converted value exceeds the Low Alarm Value, the corresponding contact and buffer is set to "Alert"

Configurable range is as shown below.

 

Output Format

Range

Unsigned Value

0 ~ 16,000

Signed Value

-8,000 ~ 8,000

Regular Value

4 ~ 20 mA

4,000 ~ 20,000

0 ~ 20 mA

0 ~ 20,000

1 ~ 5 V

1,000 ~ 5,000

0 ~ 5 V

0 ~ 5,000

-10 ~ 10 V

-10,000 ~ 10,000

0 ~ 10 V

0 ~ 10,000

Percentage

0 ~ 10,000

To disable High/Low Alarm Value feature, set both bound values to "0".