Digital Filter Constant (Address "35"-"42")

 

Address

Function

Hex

Dec

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

23H

35

Ch02 Digital Filter Constant

Ch01 Digital Filter Constant

24H

36

Ch04 Digital Filter Constant

Ch03 Digital Filter Constant

25H

37

Ch06 Digital Filter Constant

Ch05 Digital Filter Constant

26H

38

Ch08 Digital Filter Constant

Ch07 Digital Filter Constant

27H

39

Ch10 Digital Filter Constant

Ch09 Digital Filter Constant

28H

40

Ch12 Digital Filter Constant

Ch11 Digital Filter Constant

29H

41

Ch14 Digital Filter Constant

Ch13 Digital Filter Constant

30H

42

Ch16 Digital Filter Constant

Ch15 Digital Filter Constant

In case of 8-channel module, address 39~42 are not used.
Digital Filter Constant indicates a constant that is used for the digital filter calculation in range of 0 to 99. The constant stored in the address 35~42 actuall means 0.00 ~ 0.99 in the digital filter calculation.
PVn = PV + @(PVn-1-PV)
PVn : Filtered result value (This value is used as the final measurement value)
PVn-1 : Filtered result value from the last sampling
PV : Newly measured value
@ : Digital Filter Constant (0.00 ~ 0.99)