Measured Value (RAW) (Address "64"-"78")
Measured Value (RAW) (Address "64"-"78")
Address | Function | R/W | |
Hex | Dec | ||
40H | 64 | CH.1 Measured Value (RAW) | R |
41H | 65 | CH.2 Measured Value (RAW) | R |
42H | 66 | CH.3 Measured Value (RAW) | R |
43H | 67 | CH.4 Measured Value (RAW) | R |
44H | 68 | CH.5 Measured Value (RAW) | R |
45H | 69 | CH.6 Measured Value (RAW) | R |
46H | 70 | CH.7 Measured Value (RAW) | R |
47H | 71 | CH.8 Measured Value (RAW) | R |
48H | 72 | CH.9 Measured Value (RAW) | R |
49H | 73 | CH.10 Measured Value (RAW) | R |
4AH | 74 | CH.11 Measured Value (RAW) | R |
4BH | 75 | CH.12 Measured Value (RAW) | R |
4CH | 76 | CH.13 Measured Value (RAW) | R |
4DH | 77 | CH.14 Measured Value (RAW) | R |
4EH | 78 | CH.15 Measured Value (RAW) | R |
In case of 8-channel module, address 72~78 are not used.
Converts A/D converted value into Input Type value then stores the converted value.
Refer to the table below for the Input Type value’s range.
Input Type | Converted Value |
4 ~ 20 mA | 4,000 ~ 20,000 |
0 ~ 20 mA | 0 ~ 20,000 |
1 ~ 5 V | 1,000 ~ 5,000 |
0 ~ 5 V | 0 ~ 5,000 |
-10 ~ 10 V | -10,000 ~ 10,000 |
0 ~ 10 V | 0 ~ 10,000 |