DA Module

In order to write analog output value to device, it is used to set analog output value to assigned channels.

Click Online -> Special Module Setup and DA Module or click DA module on the Card Properties.

CM1 DA module and CM3 DA module have different configuration window.

Applied Module : CM1-DA04V, CM1-DA04VA, CM1-DA08V, CM1-DA08VA, CM1-DA04I and CM1-DA08I.
CM3-SP04EOAI and CM3-SP04EOAV

 

CM1 DA module

 

image-20240329-084021.png

 

Base and Slot number will appear automatically if CICON connects to PLC.

  1. If you want to set all 4 channels at once, press Ctrl and click channels.

  2. Click Enable and choose Digital Value Range and STOP mode output.
    Digital Value Range : -192 - 16191 / -8192 - +8191
    STOP mode output : Clear or Hold
    Clear - If CPU mode is STOP, the last value will be output.
    Hold – If CPU mode is STOP, ‘0’ value will be output.

  3. Click OK.

    image-20240329-084031.png

  4. Click Write to save parameter to PLC.

  5. Click to Read to check parameter.

  6. If you click Status, you can see current value, minimum and maximum value, firmware version of module and error code.

TIP : Channel Enable or Disable setting

  1. Check PLC is RUN mode.

  2. Click Status and double-click Channel number 1.

  3. Choose Enable and click OK.

  4. If PLC is turned ON, Enable for all 4channels are remained.

Example)

 

 

H0001 : DA module slot number
23 : Buffer memory 23 for DA output Enable or Disable setting
H000F : choose channel to Enable output (CH1~CH8)
1: Data word to save in buffer memory

 

  1. Click Set value and choose the Output value and click OK.

 

 

CM3 DA module : CM3-SP04EOAI, CM3-SP04EOAV

 

 

  1. Double click Channel number 1 to open Channel Setup window.
    (If you want to set all 4 channels at once, press Ctrl and click channels.)

  2. Click Enable and choose each parameters.
    Digital Value Range : 0 - 16000 / -8000 - +8000 / 0 – 10000(Percentage)
    STOP mode output : Clear, Hold, Half Level or Max. Level
    Output signal : 0 – 10 / -10 - 10 (Only SP04EOAV(Voltage) has this parameter.)

  3. Click OK.

  4. Click Write to save parameter to PLC.