AD/DA Module
In order to read analog input value and write analog output value, it is used to set analog input and output value to assigned channels.
Click Online -> Special Module Setup and AD/DA Module or click ADDA module on the Card Properties.
Applied Module : CM3-SP04EAA
AD Channel Setting
Base and Slot number will appear automatically if CICON connects to PLC.
Double click Channel number 1 to open Channel Setup window.
(If you want to set all 2 channels at once, press Ctrl and click channels.)Choose each parameters.
Signal Type (Input type) : 4 - 20mA / 0 - 20mA / 1 - 5V / 0 - 5V / -10 - +10V / 0 - 10V /
Digital Range : -8192 - +8191 / -8000 - +8000 / -192 – 16191 / 0 – 16000
Filter Constant : 0 – 100%
Sampling Time : 0 – 2550mSec
Average Window size : 0 – 255 samples
High Alarm Value : in the Digital conversion value range.
Low Alarm Value : in the Digital conversion value range.
Resolution : 14bits or 16bitsClick OK.
Click Write to save parameter to PLC.
DA Channel Setting
Double click Channel number 1 to open Channel Setup window.
(If you want to set all 2 channels at once, press Ctrl and click channels.)Click Enable and choose each parameters.
Digital Value Range : 14Bit -> 0 - 16000 / -8000 - +8000 / 0 – 10000(Percentage)
16Bit -> 0 – 64000 / -32000 - +32000 / Signal value (Current/Voltage) / 0 – 10000 (Percentage)
Output Type : 4 - 20mA / 0 - 20mA / 1 - 5V / 0 - 5V / -10 - +10V / 0 - 10V /
STOP mode output : Clear, Hold, Half Level or Max. Level
Clear - If CPU mode is STOP, the last value will be output.
Hold – If CPU mode is STOP, ‘0’ value will be output.
Resolution : 14bits or 16bits
Click OK.
Click Write to save parameter to PLC.