TC Module - Special Module Setting

In order to read temperature value and convert it to digital value, it is used to set parameter to assigned channels.

Click Online -> Special Module Setup and TC Module or click TC module on the Card Properties.

Applied Module : CM1-TC04A, CM3-SP04ETO

Channel Setting

Example) K type sensor is connected to each Channel 1 and 2 and you want to measure temperature for 4 seconds and convert average value by 0~16000.

 

image-20240329-084243.png

 

Base and Slot number will appear automatically if CICON connects to PLC.

  1. Double click Channel number 1 to open Channel Setup window.
    (If you want to set all 4 channels at once, press Ctrl and click channels.)

  2. Choose each parameters.
    TC Type : K, J, E, T, R, S, B, N, and Disable
    Digital Value Range : -192 – 16191 or -8192 - +8191
    Offset(-1000 ~ 1000) : Write offset value of measured temperature. (Buffer memory 5-8)

Example) If you write 300, Offset will be +30°C. (300 x 0.1°C)
Digital Filter : Write percentage from range 1 to 70%
Average : Choose the seconds

  1. Click OK

    image-20240329-084247.png

  2. Click Write to save the parameters.

Scale Setup

Example) Channel 1 : -100°C ~300°C Scale to 0~16000

 

 

  1. Temp. Unit : Choose °C

  2. Temperature at 0 : -100 °C

  3. Temperature at 16000 : 300 °C

  4. Click OK.