BACnet module(Slave)
Basic Setup
Applied Module : CM1-BN01A
Click Online -> Special Module Setup and choose BACnet (Slave) Module or click BACnet (Slave) module on the Card Properties.
If CPU is connected to CICON online, Base and Slot number display automatically.
If not, choose Base and Slot number where Ethernet module is installed.
Type IP Address, Subnet Mask and Gateway for your network.
Click Write to save the data.
Notice :
In case of expansion base, communication module is recommended to be installed in Local base.
If you need to install communication module in expansion base, only one communication module is recommended to be installed because communication speed (performance) should be decreasing.
BACnet Setup
To connect PLC to Master devices, set up BACnet configuration as below.
In order to respond to Master, device must be registered in Object Type.
Network Number : In order to distinguish each module in many BACnet modules on the same network, write network number. Master can find out Slave with this network number.
Click Add to register devices.
Example) Analog Input 100word from D00400.
Click Write.