RTD Module - Special Module Setting
In order to read temperature value and convert it to digital value, it is used to set parameter to assigned channels.
Click Online -> Special Module Setup and RTD Module or click RTD module on the Card Properties.
Applied Module : CM1-RD04A, CM1-RD04B and CM3-SP04ERO
Channel Setting
Example) PT100 sensor is connected to each Channel 1 and 2 and you want to measure temperature for 2 seconds and convert average value by 0~16000.
Base and Slot number will appear automatically if CICON connects to PLC.
Double click Channel number 1 to open Channel Setup window.
(If you want to set all 4 channels at once, press Ctrl and click channels.)Choose each parameters.
RTD Type : PT100, JPT100, PT1000, NI1000(DIN43760), NI1000(TER5000), Disable
Digital Value Range : -192 - 16191, -8192 - +8191, 0 – 16000, -8000 - +8000
Average : Choose the secondsClick OK
Click Write to save the parameters.
Scale Setup
Example) Channel 1 : 0°C ~ 200°C Scale
Temp. Unit : Choose °C
Temperature at 0 : 0 °C
Temperature at 16000 : 200 °C
Click OK.