RTD Module - Special Module Setting

In order to read temperature value and convert it to digital value, it is used to set parameter to assigned channels.

Click Online -> Special Module Setup and RTD Module or click RTD module on the Card Properties.

Applied Module : CM1-RD04A, CM1-RD04B and CM3-SP04ERO

Channel Setting

Example) PT100 sensor is connected to each Channel 1 and 2 and you want to measure temperature for 2 seconds and convert average value by 0~16000.

 

image-20240329-084201.png

 

Base and Slot number will appear automatically if CICON connects to PLC.

  1. Double click Channel number 1 to open Channel Setup window.
    (If you want to set all 4 channels at once, press Ctrl and click channels.)

  2. Choose each parameters.
    RTD Type : PT100, JPT100, PT1000, NI1000(DIN43760), NI1000(TER5000), Disable
    Digital Value Range : -192 - 16191, -8192 - +8191, 0 – 16000, -8000 - +8000
    Average : Choose the seconds

  3. Click OK

    image-20240329-084205.png

  4. Click Write to save the parameters.

Scale Setup

Example) Channel 1 : 0°C ~ 200°C Scale

 

 

  1. Temp. Unit : Choose °C

  2. Temperature at 0 : 0 °C

  3. Temperature at 16000 : 200 °C

  4. Click OK.