Features - PLCS RTD

RTD conversion module converts temperatures of PT100, JPT100, PT1000, NI1000 into (℃,°F) or 14bits digital value.

  1. It is used to convert temperature from PT100, JPT100, PT1000, Ni1000 into one digit number after the decimal point. It can output 0~16000 digital value.

  2. RTD module converts temperature from -200℃~600℃(PT00/PT1000/JPT100) or -50℃~160℃(Ni1000) into digital value 0~16000(-8000~8000).

  3. It can show temperature -250℃~650℃(PT00/PT1000/JPT100) or -60℃~170℃ (Ni1000). In case of digital value, it can show -192~16191(-8192 ~ 8191)

  4. If user set up Maximum and Minimum temperature value, it converts those into Minimum 0(-8000) and Maximum 16000(8000) each.

  5. There is a function that can detect thermocouple, broken cable and over range of measurement by channels.

  6. There are 4 channels (PT100, JPT100, PT1000, Ni1000) in RTD module.

  7. In case of normal status of RTD module, LED is On. In case of Error, it will be blinking by 0.3 sec.

    PT100, JPT100 : 0ºC -> 100.0Ω output
    PT1000 : 0ºC -> 1000.00Ω output
    Ni1000 : 0ºC -> 1000.00Ω output