Digital Output Setup Mode (Address "24, 25")

Buffer Memory Address "24, 25"

This is used to decide whether the range of digital output value is -192 ~ 16191, -8192 ~ 8191, 0 ~ 16000, -8000 ~ 8000.
To make this setup available, requesting to set up operation condition (Y02) is to be set and reset.
If the corresponding bit of each channel is 0, the range of values is from –192 to 16191. If it is 1, the range of values is from -8192 to 8191.
Default value is set up as 0(-192~16191).
As a set value is stored in EEPROM, the A/D module is operated as previously set value even though the power is on and off.

 

image-20240325-040600.png

 

 

Address 24

Address 25

Digital Output

0

0

-192 ~ 16191

0

1

0~16000

1

0

-8192 ~ 8191

1

1

-8000 ~ 8000