Parameters
Area that stores the parameters of high speed counter takes up 26 word memory size for each channel. These memory areas can be configured by the user out of M / L / K / D areas on the HSC for PLC-S Special Program in CICON.
If you select M100 as the Start Address of the memory on the HSC for PLC-S Special Program, the data associated with the Channel 1 is written and stored in the 26 word areas from M100 to M350. Thus, the data associated with the Channel 2 is stored subsequent to the Channel 1 data from M360 to M610 with 26 word addresses.
The parameters of each channel are allocated from the Start Address to the order described in the table below. Unless there is a remark Read Only, most of the data can be both read and written in the sequence program.
Offset | Group | Item | Configurations | Memory | Remark | |
Value | Function | |||||
0(+26) | Parameter | Count Mode | H0000 | Linear Counter | Word | Read Only |
H0001 | Ring Counter | |||||
+1(+27) | Input Pulse Type | H0000 | 2 Phase, 2 Input, 2 Multi. |
|
| |
H0001 | 2 Phase, 2 Input, 4 Multi. | |||||
H0002 | 1 Phase, 2 Multi. (Low) | |||||
H0003 | 1 Phase, 2 Multi. (High) | |||||
+2(+28) | Compare Mode | H0000 | < | Word |
| |
H0001 | <= | |||||
H0002 | = | |||||
H0003 | >= | |||||
H0004 | > | |||||
H0005 | < > | |||||
H0006 | > < | |||||
+3(+29) | Int. Preset Value | -2,147,483,648 ~ 2,147,483,647 | Dword | Low Word | ||
+4(+30) | High Word | |||||
+5(+31) | Ext. Preset Value | Low Word | ||||
+6(+32) | High Word | |||||
+7(+33) | Ring Max. Value | Low Word | ||||
+8(+34) | High Word | |||||
+9(+35) | Compare Max. | Low Word | ||||
+10(+36) | High Word | |||||
+11(+37) | Compare Min. | Low Word | ||||
+12(+38) | High Word | |||||
+13(+39) | Compare Output | HFFFF | N/A | Word |
| |
H0000 | Y0010 | |||||
H0001 | Y0011 | |||||
H0002 | Y0012 | |||||
H0003 | Y0013 | |||||
H0004 | Y0014 | |||||
H0005 | Y0015 | |||||
H0006 | Y0016 | |||||
H0007 | Y0017 | |||||
+14(+40) | Unit Time | 1~60,000 mSec |
|
| ||
+15(+41) | Pulse / Rotation | 1~60,000 Pulse |
|
| ||
+16(+42) | Control | Counter Enable | Bit 0 | SET = Enable | Word |
|
Internal Preset | Bit 1 | SET = Preset |
| |||
Ext. Preset Enable | Bit 2 | SET = Enable |
| |||
Down Counting | Bit 3 | SET = Down | Read Only | |||
Compare Output Enable | Bit 4 | SET = Enable | Read Only | |||
Select RPM / PPS | Bit 5 | RPM(1), PPS(0) |
| |||
Latch Counter | Bit 6 | SET = Enable | Read Only | |||
| Bit 7..F |
|
| |||
+17(+43) | Monitor | RPM/PPS Measured Value | -2,147,483,648 ~ 2,147,483,647 | Dword | Low Word | |
+18(+44) | High Word | |||||
+19(+45) |
|
|
|
|
| |
+20(+46) | Carry | Bit 0 | SET = Carry | Word | Read Only | |
Borrow | Bit 1 | SET = Borrow | Read Only | |||
Compare Result | Bit 2 | SET = Result | Read Only | |||
| Bit 3..F |
|
| |||
+21(+47) | Current Count Value | -2,147,483,648 ~ 2,147,483,647 | Dword | Low Word | ||
+22(+48) | High Word | |||||
+23(+49) | Input Pulse per Unit Time | -2,147,483,648 ~ 2,147,483,647 | Dword | Low Word | ||
+24(+50) | High Word | |||||
+25(+51) | Error Code | Refer to the Error Code Table | Word |
|