Wiring external counter signals
Wiring external counter signals
High Speed Counter I/O signal is activated when [Enable Count] is selected in the Special Program as shown above. If [Enable Count] is not selected, general I/O signal will be activated.
Preset input signal is activated when [Enable External Preset] is selected in the Special Program. If not selected, general input signal will be activated.
You can assign output from Y10 to Y17 as Compare Output. Compare Output will be activated when [Enable Compare Output(Y)] is selected and one of the outputs is assigned as a compare output contact.
Input Pin | Input Signal (1) | Output Signal (2) | Output Pin |
X000 | Channel 1 Phase A | Compare Output (If not used for Compare Output, these outputs can be used as digital outputs) | Y010 |
X001 | Channel 1 Phase B | Y011 | |
X002 | Channel 2 Phase A | Y012 | |
X003 | Channel 2 Phase B | Y013 | |
X004 | Channel 1 Preset Input 24V | Y014 | |
X005 |
| Y015 | |
X006 | Channel 2 Preset Input 24V | Y016 | |
X007 |
| Y017 | |
COM | Input Common | External Power Input (+) | DC24V |
COM | Input Common | Power Input Common (-) | COM |
Based on CM3-SP32MDT