External Preset Value

External Preset Value (Offset 5, 6)

When external preset input signal (Channel 1: X0004, Channel 2: X0006) is changed (Contact A) from OFF to ON, the current count value is changed to designated value in this offset.
But, in the Ring Counter Mode, if the specified value is out of the count range, the current value will not be modified despite the preset signal input (Error Code 100 occurs).