Temperature

High resolution : 1 / 16,000 (14 bits)
Simple and easy configuration with dialog box.
RTD, TC, NTC module 

 

RD**A/B module :

 

image-20240321-083601.png

 

 

image-20240321-083603.png

 

· Compatible with 3-wired Pt. 100/DIN and JIS standard type

· Self-diagnostic function detecting sensor's breakdown per channel

· High accuracy (less than 0.1% of full scale)

· Must be used with SPC or SP2B power module

 

RTD Type

RD04A / RD08A

Pt100 (KS C1640-1989, DIN 43760-1980)

JPt100 (KS C1603-1991, JIS C1604-1981)

RD04B / RD08B

Pt1000 (DIN EN 60751)

Ni1000 (DIN 43760)

Range of Input Temperatures

RD04A / RD08A

Pt100 :  -200.0 to 600oC (18.48 to 313.59W)

JPt100 :  -200.0oC to 600oC (17.14 to 317.28W)

RD04B / RD08B

Pt1000 :  -200.0oC to 600oC (184.8 to 3135.9W)

Ni1000 :  -50.0oC to 160oC (695.2 to 1986.3W)

Digital Output

Digitally Converted Value : 0 ~ 16,000(-8000~8000)

Detected Temperature Value : -2000~6000(Value of the first decimal Place X 10)

Breakdown Dtection

3 Wires by Channels

Precision

0.1 %(Full Scale)

Max. Conversion Rate

50ms / Channel

No. of Input Channels

RD04A, B

4 Channel

RD08A, B

8 Channel

Insulation Type

Photo Coupler (No Insulation between channels)

Connection Terminal

18 Points Terminal

Current

Consumption(mA)

+5V

50

+15V

30

-15V

10

 

 

 

TC04A module :

 

 

· Direct input from temperature sensor's eliminates the external transducer

· Thermocouple sensors compatible with K-J-E-B-R-S Type

· Self-diagnostic function detecting sensor's breakdown per channel

· Cold junction compensation is also equipped (automatic)

· Acceptable for worldwide standard as ANSI, DIN, BS, JIS and KS

· Must be used with SPC or SP2B power module

 

 

Model

CM1-TC04A

Available TC

K, J, E, T, B, R, S

Digital Ouput

Digitally Converted value : 0 ~ 16000(-8000~8000),

Converted Temperature Value : (Range of Measured Temperature X 10)

Range of Input Temperatures

Type of TC

Standard

Range of  Measured

Temperatures(℃)

Range of Measured Voltage

K

KS

ANSI

DIN

BS

JIS

-200.0 ~ 1200.0

-5891 ~ 48828

J

-200.0 ~ 800.0

-7890 ~ 45498

E

-200.0 ~ 600.0

-8824 ~ 45085

T

-200.0 ~ 400.0

-5602 ~ 20869

B

400.0 ~ 1800.0

786 ~ 13585

R

0.0 ~ 1750.0

0 ~ 21006

S

0.0 ~ 1750.0

0 ~ 18612

Compensation Type

Automatic Compensation

Breakdown Detection

Detection by Channels

Precision

[(Full Scale)x0.3%+1oC(error for base contact compensation)]

Max. Conversion Rate

50ms / Chennel

No. of Input Ch

4 Channel / Module

Connection Terminal

18 Points Terminal

Current

Consumption(mA)

+5V

60

+15V

30

-15V

10

 

 

 

Thermistor module :

 

 

· Max. 8 channel NTC thermistor with one module

· Possible to measure NTC (Negative Temperature Coefficient) type Thermistor

· Temperature data accuracy of one decimal place.

· For each channel, this unit could detect any thermistor's single line input and assuming over setting of input.

· In the use of the Thermistor temperature-resistance table, it is able to input desired maximum, medium and minimum temperature(C) point and Resistance(Q) to measure.

 

 

Model

CM1-TH08A

Thermistor

NTC TYPE

Range of Thermistor Input Resistance

0 ~ 1MΩ

Resolution of Thermistor Input Resistance

0Ω    ~ 40kΩ  : 1Ω

40kΩ  ~ 400kΩ : 10Ω

400kΩ ~ 1MΩ   : 30Ω

Convert range

Temperature Convert value

oC, oF (0.1oC Resolution)

Digital value

0 ~ 16000, -8000 ~ 8000

Resistance-Temperature Calculation

Steinhart-Hart thermistor polynomial

Precision

0.3%(Full Scale)

Max. Conversion Rate

1Sec(8ch)

Temperature Input Point

8 Points

Insulation method

Photo Coupler

Connection Terminal

18 Points