Temperature
High resolution : 1 / 16,000 (14 bits)
Simple and easy configuration with dialog box.
RTD, TC, NTC module
RD**A/B module :
|
| · Compatible with 3-wired Pt. 100/DIN and JIS standard type · Self-diagnostic function detecting sensor's breakdown per channel · High accuracy (less than 0.1% of full scale) · Must be used with SPC or SP2B power module |
RTD Type | RD04A / RD08A | Pt100 (KS C1640-1989, DIN 43760-1980) JPt100 (KS C1603-1991, JIS C1604-1981) | ||
RD04B / RD08B | Pt1000 (DIN EN 60751) Ni1000 (DIN 43760) | |||
Range of Input Temperatures | RD04A / RD08A | Pt100 : -200.0 to 600oC (18.48 to 313.59W) JPt100 : -200.0oC to 600oC (17.14 to 317.28W) | ||
RD04B / RD08B | Pt1000 : -200.0oC to 600oC (184.8 to 3135.9W) Ni1000 : -50.0oC to 160oC (695.2 to 1986.3W) | |||
Digital Output | Digitally Converted Value : 0 ~ 16,000(-8000~8000) Detected Temperature Value : -2000~6000(Value of the first decimal Place X 10) | |||
Breakdown Dtection | 3 Wires by Channels | |||
Precision | 0.1 %(Full Scale) | |||
Max. Conversion Rate | 50ms / Channel | |||
No. of Input Channels | RD04A, B | 4 Channel | ||
RD08A, B | 8 Channel | |||
Insulation Type | Photo Coupler (No Insulation between channels) | |||
Connection Terminal | 18 Points Terminal | |||
Current Consumption(mA) | +5V | 50 | ||
+15V | 30 | |||
-15V | 10 |
TC04A module :
| · Direct input from temperature sensor's eliminates the external transducer · Thermocouple sensors compatible with K-J-E-B-R-S Type · Self-diagnostic function detecting sensor's breakdown per channel · Cold junction compensation is also equipped (automatic) · Acceptable for worldwide standard as ANSI, DIN, BS, JIS and KS · Must be used with SPC or SP2B power module
|
Model | CM1-TC04A | ||||
Available TC | K, J, E, T, B, R, S | ||||
Digital Ouput | Digitally Converted value : 0 ~ 16000(-8000~8000), Converted Temperature Value : (Range of Measured Temperature X 10) | ||||
Range of Input Temperatures | Type of TC | Standard | Range of Measured Temperatures(℃) | Range of Measured Voltage | |
K | KS ANSI DIN BS JIS | -200.0 ~ 1200.0 | -5891 ~ 48828 | ||
J | -200.0 ~ 800.0 | -7890 ~ 45498 | |||
E | -200.0 ~ 600.0 | -8824 ~ 45085 | |||
T | -200.0 ~ 400.0 | -5602 ~ 20869 | |||
B | 400.0 ~ 1800.0 | 786 ~ 13585 | |||
R | 0.0 ~ 1750.0 | 0 ~ 21006 | |||
S | 0.0 ~ 1750.0 | 0 ~ 18612 | |||
Compensation Type | Automatic Compensation | ||||
Breakdown Detection | Detection by Channels | ||||
Precision | [(Full Scale)x0.3%+1oC(error for base contact compensation)] | ||||
Max. Conversion Rate | 50ms / Chennel | ||||
No. of Input Ch | 4 Channel / Module | ||||
Connection Terminal | 18 Points Terminal | ||||
Current Consumption(mA) | +5V | 60 | |||
+15V | 30 | ||||
-15V | 10 |
Thermistor module :
| · Max. 8 channel NTC thermistor with one module · Possible to measure NTC (Negative Temperature Coefficient) type Thermistor · Temperature data accuracy of one decimal place. · For each channel, this unit could detect any thermistor's single line input and assuming over setting of input. · In the use of the Thermistor temperature-resistance table, it is able to input desired maximum, medium and minimum temperature(C) point and Resistance(Q) to measure.
|
Model | CM1-TH08A | |
Thermistor | NTC TYPE | |
Range of Thermistor Input Resistance | 0 ~ 1MΩ | |
Resolution of Thermistor Input Resistance | 0Ω ~ 40kΩ : 1Ω 40kΩ ~ 400kΩ : 10Ω 400kΩ ~ 1MΩ : 30Ω | |
Convert range | Temperature Convert value | oC, oF (0.1oC Resolution) |
Digital value | 0 ~ 16000, -8000 ~ 8000 | |
Resistance-Temperature Calculation | Steinhart-Hart thermistor polynomial | |
Precision | 0.3%(Full Scale) | |
Max. Conversion Rate | 1Sec(8ch) | |
Temperature Input Point | 8 Points | |
Insulation method | Photo Coupler | |
Connection Terminal | 18 Points |