Digital I/O

Internal circuitary is insulated by photo-coupler of relay.
Furnish a LED Indicator.
DC Inputs , AC Inputs, Combination I/O, Relay Output & SSR Output, Transistor Output 

 

DC Inputs :

 

image-20240321-064709.png

 

 

image-20240321-064711.png

 

 

 

 

Model

CM1-XD16A

CM1-XD32C

CM1-XD64C

CM1-XD16B

CM1-XD32B

No. of Input Points

16

32

64

16

32

Rated Input Voltage

DC 24V

Rated Input Current

4mA

ON Voltage / ON Current

DC 19V / 4mA

DC 15V / 4mA

OFF Voltage / OFF Current

DC 11V / 1mA

DC 12V / 1mA

Response Time

OFF -> ON

5ms or less

ON -> OFF

5ms or less

Common Type

8 Points

Operation Indication

LED is turned on when there is input signal

Insulation Type

Photo Coupler

Input Type

SINK / SOURCE

 

 

 

AC Inputs :

 

 

 

 

 

Model

CM1 – XA08A

CM1 – XA08B

No. of Input Points

8 Points

Rated Input Voltage

AC 200 ~ 240V

AC 90 ~ 130V

Rated Input Current

9mA

5mA

ON Voltage / ON Current

AC 160V

AC 80V

OFF Voltage / OFF Current

AC 60V

AC30V

Response Time

OFF ->> ON

5ms or less

ON ->> OFF

5ms or less

Common Type

8 Points

Operation Indication

LED is turned on when there is input signal

Insulation Type

Photo Coupler

 

 

 

Combination I/O :

 

 

 

 

 

 

 

Relay Output & SSR Output :

 

 

 

 

 

 

Relay Output

SSR Output

CM1-YR16A

CM1-YR32A

CM1-YS08A

No. of Output Points (Point)

16 Points

32 Points

8 Points

Rated Load Voltage

DC 12/24V

AC100 ~ 240V

AC 220V

50 /60 Hz

Rated Load Current

1 Point

2A

1A

1Com

5A

2A

Response Time

OFF ->> ON

10ms or less

1ms or less

ON ->> OFF

5ms or less

0.5 cycle + 1ms or less

Common Type

8 Points

8 Points

Operation Indication

LED is turned ON when there is output signal

Insulation Type

Relay

Photo Coupler

 

 

 

Transistor Outputs :

 

 

 

 

 

 

 

 

 

 

 

 

CM-YT16A

CM1-YT16B

CM1-YT32A

CM1-YT32B

CM-YT64A

No. of Output Points

16/SINK

16/SRC

32/SINK

32/SRC

64/SINK

Rated Load Voltage

DC 12 ~ 24V

Rated Load Current

1Point

0.5A

0.5A

0.2A

0.2A

0.1A

1Com

4A

Response Time

OFF ->> ON

1ms or less

ON ->> OFF

1ms or less

Common Type

16 Points

16 Points

32 Points

32 Points

64 Points

Operation Indication

LED is turned on when there is output signal

Insulation Type

Photo Coupler