Communication - CM1

  • Simple and easy configuration with dialog box

  • Provides user protocol programming function for communication with other devices

  • Supports the connection through the internet (Ethernet)

  • Data link between PLSs through RS232C, RS 485 Ethernet or internet

  • Feature

    • Ethernet : Support PLC Link function for high-speed data communication among CIMON-PLC modules and enable to communicate with 64 stations as maximum at the same time.

    • RS232C/422/485 : Enable to control a PLC at a long distance with modem communication function. allows setting up diverse baud rate from 300bps to 76800bps

    • Profibus : Supports various communication speed(9.6kbps ~ 12Mbps). 1Kbyte input data can be transferred within 2ms.

    • DeviceNET : Multi-drop and T-type branch is available and improves flexibility of network installation. enables real time managing of lowest level input/output machines within network system. Able to connect with various types of slave I/O.

    • BACnet :Supports BACnet which is the standard of BAS. Supports the functionality of BACnet class 3 servers.

 

Ethernet :

 

image-20240321-064249.png

 

 

image-20240321-064253.png

 

· IComply with IEEE802.3 code

· Support protocols like SRP, ICMP, IC, TCP, UDP

· No limit on the number of the units mounted on a base.

· Support PLC Link function for high-speed data communication among CIMON-PLC modules and enable to communicate with 64 stations as maximum at the same time.

 

Item

CM1-EC01A

CM1-EC01DNP

CM1-EC04DNP

CM1-EC10A

CM1-EC10B

Media Interface

10BASE-T

10BASE-T

100BASE-TX

100BASE-FX

Baudrate

10 Mbps

100 Mbps

Media

UTP/STP

Category5

UTP/STP

Category5

UTP/STP

Category5

Auto MIDX

SC, Multi-Mode

(1310nm)

Node Distance

100m (Node<->Hub)

2km

Service Capacity

UDP 9 Services

TCP 9 Services

Single Host

4Hosts

UDP 16 Services

TCP 16 Services

S

E

R

V

I

C

E

Loader

Yes

HMI Protocol

Yes

No

Yes

MODBUS/TCP

PLC Link

(Public Net)

PLC Link

(Private Net)

No

High-Speed Link

(Private Net)

No

Yes

DNP 3.0

No

Yes

No

 

 RS232C / 422 / 485 :

 

 

 

 

· Read and write data by using an HMI protocol

· Provide communication function suitable for multi-drop configuration which is able to link 32 units as maximum

· Enable to control a PLC at a long distance with modem communication function

· Allows setting up diverse baud rate from 300bps to 76800bps

· Enable to use RS232C / RS422 (RS485)) communication port by setting p as a independent channel or a linked channel.

· Support 1:1 / 1:N / N:M communication (In case of using RS422 channel)

· Support full-duplex (RS422) and half-duplex (RS485) communication form

· Enable to use RS485 channel as RS485 multi-drop communication channel through the parameter setup

· Support DNP 3.0 protocol (CM1-SC01DNP)

· Equipped with self-diagnosis function  and loop-back diagnosis function for diagnosing a breakdown simply

 

 

Model

CM1-SC01A

CM1-SC01B

CM1-SC02A

CM1-SC01DNP

Interface

RS232C

RS422/485

RS232C/422/485

RS232C

Comm

Mode

HMIMode

CIMON HMI Protocol(Supports 1 : n Communication)

-

Loader Mode

CICON Communication

-

MODBUS

MODBUS RTU Mode(Slave and Master)

-

DNP

-

DNP 3.0 Protocol

User definition Mode

Protocol Program

 

Form of Data

Data Bit

7 or 8 Bit

Stop Bit

1 or 2 Bit

Parity

Even / odd / None

Sync

Asynchronous

Baud Rate

300 / 600 / 1200 / 2400 / 4800 / 9600 / 19200 / 38400 / 76800

Modem Link

Long-distance communication by linking with a modem unit

 

 Profibus DP module :

Profibus is manufacturer selective (vendor independence) and is used vastly for work Automization as an open type fieldbus. The characteristics of open type are sated in Europe standard EN501070 and EN50204. Profibus enables communication between different manufacturer’s devices without any special interface required. Profibus is very efficient and highly on conditions where careful consideration is required to communicate in complex and high speed environment. Even when more advanced technology comes in effect, Profibus will be the industrial communication system who will be ready for the futrure.

 

 

 

 

· Suitable to communicate between Master Automation Machine and Scatter Slave I/O Machine.

· Supports various communication speed (9.6kbps - 12Mbps)

· RS485 Communication method is used

· Field construction made easier due to use of Twisted Pair Cable

· Supports Maximum of 127 station (32 per segment)

· Network setup is done with Configuration tool

· 1Kbyte input data can be transferred within 2ms

· Data transition can be done with order or without order

· Individual or Multi master network function available

 

 

CM1-PD01A

CM1-PD01B

Interface

RS 485

Network

Profibus DP

Media Access

Token Passing & Polling

Cable

Two wire Shielded twisted pair cable

Number of Max slave connection/network

127

Number of Max slave connection/segment

32

Max. I/O Data slave

244 Byte

Max. I/O Data

I/O 3,584 Byte each

I/O 512 Byte each

Configuration Tool

Sycon-PB

Configuration Port

RS232C

Communication Parameter setting

High-speed link parameter communication setting

 

Transmission

9.6K(bps)

19.2K

93.75K

187.5K

500K

1,500K

12,000K

Distance

1200m

1200m

1200m

1000m

400m

200m

100m

 

 

DeviceNet module :

Open type communication standard DeviceNet enables compatibility among different manufactures' similar typed components.

 

 

 

· Machine I/O is high speed network of open structure by choosing Global Standard DeviceNet.

· Multi-drop and T-type branch is available and improves flexibility of network installation

· One network module can manage 63 slave modules and maximum 57334 points of I/O

· Enables real time managing of lowest level input/output machines within network system

· Functions such as seguence managing, processing managing and motion managing can be used in many different fields of managing sites.

· Able to connect with various types of slave I/O

· Max 4 master modules are applicable with one CPU.

 

 

BACnet module :

Abbreviation of Building Automation and Control Networks and is open-type standard protocol for the building auto-control.

· Supports BACnet which is the standard of building automated system.

· Supports the functionality of BACnet class 3 servers.

· chose Ethernet for communication Physical layer.

 

 

Model

CM1-BN01A

Protocol size

ANSI / ASHRAE 135-1995 (KS X 6909)

Protocol stack

UDP/IP

Physical Standard

ISO / IEC8802-3 (IEEE 802.3, CSMA/CD, 10BASE-T)

Data transfer speed

10 Mbps

Transfer method

Base Band

Max/ Segment length

100m

Max. I/O data slave

244 Byte