Communication - CM1
Simple and easy configuration with dialog box
Provides user protocol programming function for communication with other devices
Supports the connection through the internet (Ethernet)
Data link between PLSs through RS232C, RS 485 Ethernet or internet
Feature
Ethernet : Support PLC Link function for high-speed data communication among CIMON-PLC modules and enable to communicate with 64 stations as maximum at the same time.
RS232C/422/485 : Enable to control a PLC at a long distance with modem communication function. allows setting up diverse baud rate from 300bps to 76800bps
Profibus : Supports various communication speed(9.6kbps ~ 12Mbps). 1Kbyte input data can be transferred within 2ms.
DeviceNET : Multi-drop and T-type branch is available and improves flexibility of network installation. enables real time managing of lowest level input/output machines within network system. Able to connect with various types of slave I/O.
BACnet :Supports BACnet which is the standard of BAS. Supports the functionality of BACnet class 3 servers.
Ethernet :
|
| · IComply with IEEE802.3 code · Support protocols like SRP, ICMP, IC, TCP, UDP · No limit on the number of the units mounted on a base. · Support PLC Link function for high-speed data communication among CIMON-PLC modules and enable to communicate with 64 stations as maximum at the same time. |
Item | CM1-EC01A | CM1-EC01DNP | CM1-EC04DNP | CM1-EC10A | CM1-EC10B | |
Media Interface | 10BASE-T | 10BASE-T 100BASE-TX | 100BASE-FX | |||
Baudrate | 10 Mbps | 100 Mbps | ||||
Media | UTP/STP Category5 | UTP/STP Category5 | UTP/STP Category5 Auto MIDX | SC, Multi-Mode (1310nm) | ||
Node Distance | 100m (Node<->Hub) | 2km | ||||
Service Capacity | UDP 9 Services TCP 9 Services | Single Host | 4Hosts | UDP 16 Services TCP 16 Services | ||
S E R V I C E | Loader | Yes | ||||
HMI Protocol | Yes | No | Yes | |||
MODBUS/TCP | ||||||
PLC Link (Public Net) | ||||||
PLC Link (Private Net) | No | |||||
High-Speed Link (Private Net) | No | Yes | ||||
DNP 3.0 | No | Yes | No |
RS232C / 422 / 485 :
| · Read and write data by using an HMI protocol · Provide communication function suitable for multi-drop configuration which is able to link 32 units as maximum · Enable to control a PLC at a long distance with modem communication function · Allows setting up diverse baud rate from 300bps to 76800bps · Enable to use RS232C / RS422 (RS485)) communication port by setting p as a independent channel or a linked channel. · Support 1:1 / 1:N / N:M communication (In case of using RS422 channel) · Support full-duplex (RS422) and half-duplex (RS485) communication form · Enable to use RS485 channel as RS485 multi-drop communication channel through the parameter setup · Support DNP 3.0 protocol (CM1-SC01DNP) · Equipped with self-diagnosis function and loop-back diagnosis function for diagnosing a breakdown simply |
Model | CM1-SC01A | CM1-SC01B | CM1-SC02A | CM1-SC01DNP | |
Interface | RS232C | RS422/485 | RS232C/422/485 | RS232C | |
Comm Mode | HMIMode | CIMON HMI Protocol(Supports 1 : n Communication) | - | ||
Loader Mode | CICON Communication | - | |||
MODBUS | MODBUS RTU Mode(Slave and Master) | - | |||
DNP | - | DNP 3.0 Protocol | |||
User definition Mode | Protocol Program |
| |||
Form of Data | Data Bit | 7 or 8 Bit | |||
Stop Bit | 1 or 2 Bit | ||||
Parity | Even / odd / None | ||||
Sync | Asynchronous | ||||
Baud Rate | 300 / 600 / 1200 / 2400 / 4800 / 9600 / 19200 / 38400 / 76800 | ||||
Modem Link | Long-distance communication by linking with a modem unit |
Profibus DP module :
Profibus is manufacturer selective (vendor independence) and is used vastly for work Automization as an open type fieldbus. The characteristics of open type are sated in Europe standard EN501070 and EN50204. Profibus enables communication between different manufacturer’s devices without any special interface required. Profibus is very efficient and highly on conditions where careful consideration is required to communicate in complex and high speed environment. Even when more advanced technology comes in effect, Profibus will be the industrial communication system who will be ready for the futrure.
| · Suitable to communicate between Master Automation Machine and Scatter Slave I/O Machine. · Supports various communication speed (9.6kbps - 12Mbps) · RS485 Communication method is used · Field construction made easier due to use of Twisted Pair Cable · Supports Maximum of 127 station (32 per segment) · Network setup is done with Configuration tool · 1Kbyte input data can be transferred within 2ms · Data transition can be done with order or without order · Individual or Multi master network function available |
| CM1-PD01A | CM1-PD01B |
Interface | RS 485 | |
Network | Profibus DP | |
Media Access | Token Passing & Polling | |
Cable | Two wire Shielded twisted pair cable | |
Number of Max slave connection/network | 127 | |
Number of Max slave connection/segment | 32 | |
Max. I/O Data slave | 244 Byte | |
Max. I/O Data | I/O 3,584 Byte each | I/O 512 Byte each |
Configuration Tool | Sycon-PB | |
Configuration Port | RS232C | |
Communication Parameter setting | High-speed link parameter communication setting |
Transmission | 9.6K(bps) | 19.2K | 93.75K | 187.5K | 500K | 1,500K | 12,000K |
Distance | 1200m | 1200m | 1200m | 1000m | 400m | 200m | 100m |
DeviceNet module :
Open type communication standard DeviceNet enables compatibility among different manufactures' similar typed components.
| · Machine I/O is high speed network of open structure by choosing Global Standard DeviceNet. · Multi-drop and T-type branch is available and improves flexibility of network installation · One network module can manage 63 slave modules and maximum 57334 points of I/O · Enables real time managing of lowest level input/output machines within network system · Functions such as seguence managing, processing managing and motion managing can be used in many different fields of managing sites. · Able to connect with various types of slave I/O · Max 4 master modules are applicable with one CPU. |
BACnet module :
Abbreviation of Building Automation and Control Networks and is open-type standard protocol for the building auto-control.
· Supports BACnet which is the standard of building automated system. · Supports the functionality of BACnet class 3 servers. · chose Ethernet for communication Physical layer. |
Model | CM1-BN01A |
Protocol size | ANSI / ASHRAE 135-1995 (KS X 6909) |
Protocol stack | UDP/IP |
Physical Standard | ISO / IEC8802-3 (IEEE 802.3, CSMA/CD, 10BASE-T) |
Data transfer speed | 10 Mbps |
Transfer method | Base Band |
Max/ Segment length | 100m |
Max. I/O data slave | 244 Byte |