Module Specifications - RTD Module
Item | Specification | ||
Available RTD | RD04A | Pt 100 (JIS C1640-1989, DIN 43760-1980) JPt100 (KS C1603-1991, JIS C1604-1981) | |
RD04B | Pt1000 (DIN EN 60751) | ||
Range of Temperature Input | RD04A | Pt 100 : -200.0oC to 600oC (18.48 to 313.59W) JPt100 : -200.0oC to 600oC (17.14 to 317.28W) | |
RD04B | Pt1000 : -200.0oC to 600oC (185.201 to 3137.080W) | ||
Digital Output | Digitally Converted Value : 0 ~ 16,000(-8000~8000) Detected Temperature Value : -2000~6000(First Decimal Place Value X 10 times) | ||
Detecting the breaking of wires | 3 wires by channels available | ||
Accuracy | 0.3%(Full Scale) | ||
Max. Conversion Rate | 50ms / channel | ||
Number of Temperature Input Points | 4 channels / module | ||
Insulation Type | Between input terminal and PLC : Photo Coupler Insulation Between output channels : No Insulation | ||
Contact Terminal | 18-point Terminal Block | ||
Internal Current (mA) | +5V | 50 | |
+15V | 30 | ||
-15V | 10 |