Redundant System
Redundancy of CPU module, power modules, bases, and communication modules is available.
CPU redundancy system is composed of separate bases for ideal redundancy structure.
In case an error occurs in an active CPU module, a back-up module is automatically converted to active one for continuous operation.
Furnishes a test button to check and maintain a system easily.
Enables the configuration of network redundancy.
Enables backup within the control scan delay time of 50ms and high-speed active conversion.
Enables to construct redundancy network with a high-ranking computer.
Supports Power redundancy.
Basic Composition of Redundancy Base :
Base | Composition Unit | Applicable Module |
CPU | Base | All base modules |
Power | All power modules | |
CPU | CM1-XP1R | |
Redundancy Interface | CM1-RM01A | |
Redundancy Comm. Module | CM1-RC01A | |
Redundancy Cable | CM0-CBE | |
Communication Module | CM1-All comm. modules including CM1-EC01A | |
Expansion | Expansion Cable | CM0-CBE |
Expansion 1 | CM1-EP03A or CM1-EP02A | |
Expansion 2 or More | CM1-EP02A or CM1-EP01A | |
Base / Power / I/O | Modules of all kinds |
System Configuration :
CM1-RPW (Redundant Power Monitoring Module) :
Power status is visualized by LEDs.
Power status signals are provided by digital output (DC 24V, Transistor, Sink)
Base for power redundancy :
Three types of bases are provided for power redundancy
Model | No. of slots | Size (mm) |
CM1-BS05R | 5 slots | 314.7 * 108 |
CM1-BS08R | 8 slots | 411.7 * 108 |
CM1-BS10R | 10 slots | 475.7 * 108 |