Redundant System

  • Redundancy of CPU module, power modules, bases, and communication modules is available.

  • CPU redundancy system is composed of separate bases for ideal redundancy structure.

  • In case an error occurs in an active CPU module, a back-up module is automatically converted to active one for continuous operation.

  • Furnishes a test button to check and maintain a system easily.

  • Enables the configuration of network redundancy.

  • Enables backup within the control scan delay time of 50ms and high-speed active conversion.

  • Enables to construct redundancy network with a high-ranking computer.

  • Supports Power redundancy.

 

Basic Composition of Redundancy Base :

 

image-20240321-061727.png

 

Base

Composition Unit

Applicable Module

CPU

Base

All base modules

Power

All power modules

CPU

CM1-XP1R

Redundancy Interface

CM1-RM01A

Redundancy Comm. Module

CM1-RC01A

Redundancy Cable

CM0-CBE

Communication Module

CM1-All comm. modules including CM1-EC01A

Expansion

Expansion Cable

CM0-CBE

Expansion 1

CM1-EP03A or CM1-EP02A

Expansion 2 or More

CM1-EP02A or CM1-EP01A

Base / Power / I/O

Modules of all kinds

 

System Configuration :

 

image-20240321-063349.png

 

CM1-RPW (Redundant Power Monitoring Module) :

  • Power status is visualized by LEDs.

  • Power status signals are provided by digital output (DC 24V, Transistor, Sink)

 

Base for power redundancy :

Three types of bases are provided for power redundancy

Model

No. of slots

Size (mm)

CM1-BS05R

5 slots

314.7 * 108

CM1-BS08R

8 slots

411.7 * 108

CM1-BS10R

10 slots

475.7 * 108