Specification of RTD module

 

Item

Specification

RTD type

Pt100 (JIS C1640-1989, DIN 43760-1980)

JPt100 (KS C1603-1991, JIS C1604-1981)

Pt1000 (DIN EN 60751)

Ni1000 (DIN 43760)

Ni1000 (TCR 5000)

Range of input temperature

Pt100 :  -200.0℃ to 600℃(18.48 to 313.59)

JPt100 :  -200.0℃to 600℃ (17.14 to 317.28)

Pt1000 :  -200.0℃ to 600℃ (184.8 to 3135.9)

Ni1000 (DIN 43760): -50.0℃ to 160℃ (742.6 to 2065.9)

Ni1000 (TCR 5000): -50.0℃ to 160℃ (790.9 to 1863.6)

Digital/Temp. Output

Digital conversion value : 0 ~ 16,000(-8000~8000)

Temp.  : -2000 ~ 6000 or -500 ~ 1600 (floating point X 10)

Disconnection detection

3 points indication for each channel

Accuracy

0.1 %(Full Scale)

Max. conversion speed

120ms

Number of Input channels

4Channel / 1 Module

Insulation Method

Photo-coupler insulation : between input terminal and PLC (No insulation between channels)

Connection Terminal

12 points

Consumption current

+ 5V

60 mA

+ 24V

30 mA