Specification of RTD module
Item | Specification | |
RTD type | Pt100 (JIS C1640-1989, DIN 43760-1980) JPt100 (KS C1603-1991, JIS C1604-1981) Pt1000 (DIN EN 60751) Ni1000 (DIN 43760) Ni1000 (TCR 5000) | |
Range of input temperature | Pt100 : -200.0℃ to 600℃(18.48 to 313.59) JPt100 : -200.0℃to 600℃ (17.14 to 317.28) Pt1000 : -200.0℃ to 600℃ (184.8 to 3135.9) Ni1000 (DIN 43760): -50.0℃ to 160℃ (742.6 to 2065.9) Ni1000 (TCR 5000): -50.0℃ to 160℃ (790.9 to 1863.6) | |
Digital/Temp. Output | Digital conversion value : 0 ~ 16,000(-8000~8000) Temp. : -2000 ~ 6000 or -500 ~ 1600 (floating point X 10) | |
Disconnection detection | 3 points indication for each channel | |
Accuracy | 0.1 %(Full Scale) | |
Max. conversion speed | 120ms | |
Number of Input channels | 4Channel / 1 Module | |
Insulation Method | Photo-coupler insulation : between input terminal and PLC (No insulation between channels) | |
Connection Terminal | 12 points | |
Consumption current | + 5V | 60 mA |
+ 24V | 30 mA |