CPU - CM1
Specification(UP Series)
Item | Specification | |||
CM1-UP1F | CM1-UP2F | CM1-UP3F | ||
Program Control Method | Repetitive operation, Stored Program (ROM mode), Periodic operation | |||
I/O Control Method | Scan synchronous batch processing system (I/O refresh), Indirect method, Direct method by instruction | |||
Program Language | IL (Instruction List), LD (Ladder Diagram), FBD (Function Block Diagram), FBD Extension, ST (Structured Text) | |||
SFC(Sequential Function Chart) | ||||
Number of Instructions | Basic | approx. 60 | ||
Application | approx. 480 | |||
Data Processing | LD | 0.075us / Step | ||
MOV | 0.049us / Step | |||
Floating-point Arithmetic | +, -, x, / 0.050 µs/Instruction | |||
Program Memory | 7M Byte (Upload, Parameter, System) | |||
Number of Program Blocks | Scan, Special, Comm., SFC Program: Max. 128 blocks. Max 65,530 steps per block (PID) ST Program: Max. 128 blocks | |||
Number of I/O | 16,384 | 8,192 | 4,096 | |
Number of I/O Devices | 16,384 | 8,192 | 4,096 | |
Supporting Program | LD | Scan, Subroutine, Initialize (COLD), Initialize (HOT), Periodic interrupt | ||
Special Configuration | Initializing special card, PID control, Thermistor setting, Loadcell setting, I/O Input module filter setting | |||
Communication | User protocol (Serial), User protocol (Ethernet), MODBUS TCP/RTU Master/Slave, Ethernet High-speed link, CIMON-NET Master/Slave, DNP3, Public network IP setting, Fieldbus, OPC UA Server | |||
SFC | SFC Program | |||
ST | ST Program (ST-only local variables/global variables) | |||
Periodic Interruption | Maximum 15, cycle setting (10–60,000 ms, Unit :10 ms), priority setting (0–14) | |||
Base Expansion | Local Base + Max. 31 Expansions (Line-Expansion) | |||
Max. Distance | Electricity (100 m) | |||
Redundancy | - | |||
Operation modes | LOCAL/Remote (RUN, STOP, PAUSE), Switch (RUN, STOP, Pause/RM) | |||
Restarting | Cold, Hot Restart | |||
Self-Diagnosis | Monitoring Process Delay, Memory Errors, I/O Errors, Power Errors, Battery Errors | |||
Data Preservation Against Power Failure | K device and conservation (Latch) in M, L, T, C, S, D device | |||
Watch Dog Timer (WDT) | 10–5000 ms (Unit: 10 ms) | |||
Timer | Cycle: 0.01 second–6553.5 seconds (10 or 100 ms) On Delay, Off Delay, Integration, Monostable, Retriggerable | |||
Counter | Counter Range: -32,768–32,767 UP, DOWN, UP/DOWN, RING COUNTER | |||
PID | 32 Channels, Auto-Tuning | |||
Communication Channels | USB | Serial: Loader Protocol only | ||
Serial | RS-232C (Max. 115,200 bps), Supported Protocols: CICON Loader, CIMON-HMI, MODBUS RTU Slave | |||
Ethernet | Speed: 10/100/1000 Mbps Expansion or Ethernet Comm. (Port A: Ethernet Comm., Port B: Expansion) Supported Comm. (Ethernet): CICON Loader, CIMON-HMI, MODBUS TCP Slave | |||
Event log | Maximum 100 (Power, Mode, Error) | |||
Firmware Upgrade | Supported | |||
Power | 5 Vdc, less than 250 mA | |||
Weight (g) | 130 g (±5 g) | |||
Floating-point Arithmetic | Supports floating-point arithmetic instructions | |||
Additional Features | I/O Reservation, PLC-LINK, RTC, Online Edit,Program download via SD Card, Whole system backup/recovery, Device backup/recovery, System log backup | |||
Capacity of Scan Program | 256k steps | 128k steps | 128k steps | |
Device Memory
| X | 16,384 | 8,192 | 4,096 |
Y | 16,384 | 8,192 | 4,096 | |
M | 65,536 Points | |||
K | 65,536 Points | |||
L | 65,536 Points | |||
F | 4,096 Points | |||
T | 4,096 (select between 10 ms and 100 ms) | |||
C | 4,096 | |||
S | 100Card*100Step | |||
D | 32,767 Words | |||
Z | 1,024 Words | |||
Q | 8,192 Points | |||
R | 16 Word |
Specification(XP Series)
Item | Specification | |||
CM1-XP1F/U | CM1-XP2F/U | CM1-XP3F/U | ||
Program Control Method | Repetitive operation, Stored Program (ROM mode), Periodic operation | |||
I/O Control Method | Scan synchronous batch processing system (I/O refresh), Indirect method, Direct method by instruction | |||
Program Language | IL (Instruction List), LD (Ladder Diagram), FBD (Function Block Diagram), FBD Extension | |||
SFC(Sequential Function Chart) | ||||
Number of Instructions | Basic | 60 | ||
Application | 480 | |||
Data Processing | LD | 0.028us / Step | ||
Floating-point Arithmetic | +, -, x, / 0.4 µs/Instruction | |||
Program Memory | 7M Byte (Upload, Parameter, System) | |||
Number of Program Blocks | Max 128, up to 65,530 steps per block (PID) | |||
Number of I/O | 8,192 | 4,092 | 2,048 | |
Number of I/O Devices | Input: 131,072 points, Output: 131,072 points | |||
Supporting Program | LD | Scan, Subroutine, Initialize (COLD), Initialize (HOT), Periodic interrupt | ||
Special Configuration | Initializing special card, PID control, Thermistor setting, Loadcell setting, I/O Input module filter setting | |||
Communication | User protocol (Serial), User protocol (Ethernet), MODBUS TCP/RTU Master/Slave, Ethernet High-speed link, CIMON-NET Master/Slave, DNP3, Public network IP setting, Fieldbus, OPC UA Server | |||
SFC | SFC Program | |||
Periodic Interruption | Maximum 15, cycle setting (10–60,000 ms, Unit :10 ms), priority setting (0–14) | |||
Base Expansion | Maximum 16, Ring topology | |||
Max. Distance | Electricity (100 m) | |||
Redundancy | - | |||
Operation modes | LOCAL/Remote(RUN, STOP, PAUSE) | |||
Restarting | Cold, Hot Restart | |||
Self-Diagnosis | Monitoring delay of processing, problems of memory, I/O, battery, power error | |||
Data Preservation Against Power Failure | K device and conservation (Latch) in M, L, T, C, S, D device | |||
Watch Dog Timer (WDT) | Maximum 5000 ms (Unit: 10 ms) | |||
Timer | On Delay, Off Delay, Addition, Monostable, Retriggerable Cycle: Either 10 or 100 ms TC (Current value)/TS (Setting value) | |||
Counter | UP, DOWN, UP/DOWN, RING COUNTER, CC (Current value)/CS (Setting value) No limitation on number of points, Count range: -32,768–32,767 | |||
PID | 32 Channels, Auto-Tuning | |||
Communication Channels | USB | USB 2.0 Mini-B: For Loader Protocol | ||
Serial | RS-232C (Maximum 115,200 bps): CICON Loader, CIMON-HMI, MODBUS RTU Slave | |||
Ethernet | Expanded/Built-in Ethernet :10/100Base-T/TX, -FX Built-in Ethernet: CICON Loader, CIMON-HMI, Modbus TCP Slave *Available to use Built-in Ethernet when nonuse of expansion | |||
Event log | Maximum 100 (Power, Mode, Error) | |||
Firmware Upgrade | Available | |||
Power | 5Vdc, 220mA | |||
Weight (g) | 138g | |||
Floating-point Arithmetic | Supporting instructions for floating-point arithmetic | |||
Capacity of Scan Program | 128K Steps | |||
Device Memory
| X | 8,192 | 4,096 | 2,048 |
Y | 8,192 | 4,096 | 2,048 | |
M | 16,000 | |||
K | 16,000 | |||
L | 16,000 | |||
F | 2,048 | |||
T | 4,096 (select between 10 ms and 100 ms) | |||
C | 4,096 | |||
S | 100Card*100Step | |||
D | 32,000 Word | |||
Z | 2,048 Word | |||
Q | 512 Word | |||
R | 16 Word |
Item | Specification | |||
CM1-XP1E | CM1-XP2E | CM1-XP3E | ||
Program Control Method | Repetitive operation, Stored Program (ROM mode), Periodic operation | |||
I/O Control Method | Scan synchronous batch processing system (I/O refresh), Indirect method, Direct method by instruction | |||
Program Language | IL (Instruction List), LD (Ladder Diagram), FBD (Function Block Diagram), FBD Extension | |||
SFC(Sequential Function Chart) | ||||
Number of Instructions | Basic | 60 | ||
Application | 480 | |||
Data Processing | LD | 0.028us / Step | ||
Floating-point Arithmetic | +, -, x, / 0.4 µs/Instruction | |||
Program Memory | 7M Byte (Upload, Parameter, System) | |||
Number of Program Blocks | Max 128, up to 65,530 steps per block (PID) | |||
Number of I/O | 8,192 | 4,092 | 2,048 | |
Number of I/O Devices | Input: 131,072 points, Output: 131,072 points | |||
Supporting Program | LD | Scan, Subroutine, Initialize (COLD), Initialize (HOT), Periodic interrupt | ||
Special Configuration | Initializing special card, PID control, Thermistor setting, Loadcell setting, I/O Input module filter setting | |||
Communication | User protocol (Serial), User protocol (Ethernet), MODBUS TCP/RTU Master/Slave, Ethernet High-speed link, CIMON-NET Master/Slave, DNP3, Public network IP setting, Fieldbus, OPC UA Server | |||
SFC | SFC Program | |||
Periodic Interruption | Maximum 15, cycle setting (10–60,000 ms, Unit :10 ms), priority setting (0–14) | |||
Base Expansion | Maximum 16 (10/100Base-T/TX) | |||
Max. Distance | Electricity (100 m) | |||
Redundancy | - | |||
Operation modes | LOCAL/Remote(RUN, STOP, PAUSE) | |||
Restarting | Cold, Hot Restart | |||
Self-Diagnosis | Monitoring delay of processing, problems of memory, I/O, battery, power error | |||
Data Preservation Against Power Failure | K device and conservation (Latch) in M, L, T, C, S, D device | |||
Watch Dog Timer (WDT) | Maximum 5000 ms (Unit: 10 ms) | |||
Timer | On Delay, Off Delay, Addition, Monostable, Retriggerable Cycle: Either 10 or 100 ms TC (Current value)/TS (Setting value) | |||
Counter | UP, DOWN, UP/DOWN, RING COUNTER, CC (Current value)/CS (Setting value) No limitation on number of points, Count range: -32,768–32,767 | |||
PID | 32 Channels, Auto-Tuning | |||
Communication Channels | USB | USB 2.0 Mini-B: For Loader Protocol | ||
Serial | RS-232C (Maximum 115,200 bps): CICON Loader, CIMON-HMI, MODBUS RTU Slave | |||
Event log | Power, Mode, Error | |||
Firmware Upgrade | Available | |||
Power | 5Vdc, 220mA | |||
Weight (g) | 138g | |||
Floating-point Arithmetic | Supporting instructions for floating-point arithmetic | |||
Capacity of Scan Program | 128K Steps | |||
Device Memory
| X | 8,192 | 4,096 | 2,048 |
Y | 8,192 | 4,096 | 2,048 | |
M | 16,000 | |||
K | 16,000 | |||
L | 16,000 | |||
F | 2,048 | |||
T | 4,096 (select between 10 ms and 100 ms) | |||
C | 4,096 | |||
S | 100Card*100Step | |||
D | 32,000 Word | |||
Z | 2,048 Word | |||
Q | 512 Word | |||
R | 16 Word |
Item | Specification | |||
CM1-XP1A | CM1-XP2A | CM1-XP3A | ||
Program Control Method | Repetitive operation, Stored Program (ROM mode), Periodic operation | |||
I/O Control Method | Scan synchronous batch processing system (I/O refresh), Indirect method, Direct method by instruction | |||
Program Language | IL (Instruction List), LD (Ladder Diagram), FBD (Function Block Diagram), FBD Extension | |||
SFC(Sequential Function Chart) | ||||
Number of Instructions | Basic | 60 | ||
Application | 480 | |||
Data Processing | LD | 0.075us / Step | ||
Floating-point Arithmetic | +, -, x, / 0.4 µs/Instruction | |||
Program Memory | 7M Byte (Upload, Parameter, System) | |||
Number of Program Blocks | Max 128, up to 65,530 steps per block (PID) | |||
Number of I/O | 8,192 | 4,092 | 2,048 | |
Number of I/O Devices | Input: 131,072 points, Output: 131,072 points | |||
Supporting Program | LD | Scan, Subroutine, Initialize (COLD), Initialize (HOT), Periodic interrupt | ||
Special Configuration | Initializing special card, PID control, Thermistor setting, Loadcell setting, I/O Input module filter setting | |||
Communication | User protocol (Serial), User protocol (Ethernet), MODBUS TCP/RTU Master/Slave, Ethernet High-speed link, CIMON-NET Master/Slave, DNP3, Public network IP setting, Fieldbus | |||
Periodic Interruption | Maximum 15, cycle setting (10–60,000 ms, Unit :10 ms), priority setting (0–14) | |||
Base Expansion | Maximum 16 (10Base-T) | |||
Max. Distance | Electricity (100 m) | |||
Redundancy | - | |||
Operation modes | LOCAL/Remote(RUN, STOP, PAUSE) | |||
Restarting | Cold, Hot Restart | |||
Self-Diagnosis | Monitoring delay of processing, problems of memory, I/O, battery, power error | |||
Data Preservation Against Power Failure | K device and conservation (Latch) in M, L, T, C, S, D device | |||
Watch Dog Timer (WDT) | Maximum 5000 ms (Unit: 10 ms) | |||
Timer | On Delay, Off Delay, Addition, Monostable, Retriggerable Cycle: Either 10 or 100 ms TC (Current value)/TS (Setting value) | |||
Counter | UP, DOWN, UP/DOWN, RING COUNTER, CC (Current value)/CS (Setting value) No limitation on number of points, Count range: -32,768–32,767 | |||
PID | 32 Channels, Auto-Tuning | |||
Communication Channels | USB | USB 2.0 B Type: For Loader Protocol | ||
Serial | RS-232C (Maximum 38,400 bps): CICON Loader / Type: RJ11 | |||
Event log | Power, Mode, Error | |||
Firmware Upgrade | Available | |||
Power | 5Vdc, 220mA | |||
Weight (g) | 138g | |||
Floating-point Arithmetic | Supporting instructions for floating-point arithmetic | |||
Capacity of Scan Program | 128K Steps | |||
Device Memory
| X | 8,192 | 4,096 | 2,048 |
Y | 8,192 | 4,096 | 2,048 | |
M | 16,000 | |||
K | 16,000 | |||
L | 16,000 | |||
F | 2,048 | |||
T | 4,096 (select between 10 ms and 100 ms) | |||
C | 4,096 | |||
S | 100Card*100Step | |||
D | 32,000 Word | |||
Z | 2,048 Word | |||
R | 16 Word |
Specification(CP Series)
Item | Specification | |||
CM1-CP3E | CM1-CP4E | CM1-CP4F | ||
Program Control Method | Repetitive operation, Stored Program (ROM mode), Periodic operation | |||
I/O Control Method | Scan synchronous batch processing system (I/O refresh), Indirect method, Direct method by instruction | |||
Program Language | IL (Instruction List), LD (Ladder Diagram), FBD (Function Block Diagram), FBD Extension | |||
SFC(Sequential Function Chart) | ||||
Number of Instructions | Basic | 60 | ||
Application | 480 | |||
Data Processing | LD | 0.084us / Step | 0.2us / Step | |
Program Memory | 512 Kbyte | 256 Kbyte | ||
Number of Program Blocks | Max 128, up to 65,530 steps per block (PID) | |||
Number of I/O | 1,536 | 384 | ||
Number of I/O Devices | 32,768 | 8,192 | ||
Supporting Program | LD | Scan, Subroutine, Initialize (COLD), Initialize (HOT), Periodic interrupt | ||
Special Configuration | Initializing special card, PID control, Thermistor setting, Loadcell setting, I/O Input module filter setting | |||
Communication | User protocol (Serial), User protocol (Ethernet), MODBUS TCP/RTU Master/Slave, Ethernet High-speed link, CIMON-NET Master/Slave, DNP3, Public network IP setting, Fieldbus, OPC UA Server | |||
SFC | SFC Program | |||
Periodic Interruption | Maximum 15, cycle setting (10–60,000 ms, Unit :10 ms), priority setting (0–14) | |||
Base Expansion | Maximum 16 (10Base-T) | - | ||
Max. Distance | Electricity (100 m) | - | ||
Redundancy | - | |||
Operation modes | LOCAL/Remote(RUN, STOP, PAUSE) | |||
Restarting | Cold, Hot Restart | |||
Self-Diagnosis | Monitoring delay of processing, problems of memory, I/O, battery, power error | |||
Data Preservation Against Power Failure | K device and conservation (Latch) in M, L, T, C, S, D device | |||
Watch Dog Timer (WDT) | Maximum 5000 ms (Unit: 10 ms) | |||
Timer | On Delay, Off Delay, Addition, Monostable, Retriggerable Cycle: Either 10 or 100 ms TC (Current value)/TS (Setting value) | |||
Counter | UP, DOWN, UP/DOWN, RING COUNTER, CC (Current value)/CS (Setting value) No limitation on number of points, Count range: -32,768–32,767 | |||
PID | 32 Channels, Auto-Tuning | |||
Communication Channels | USB | USB 2.0 B Mini-B: For Loader Protocol | ||
Serial | RS-232C (Maximum 38,400 bps): CICON Loader, CIMON-HMI, MODBUS RTU Slave / Type: Terminal Block |
- | RS-485 (Maximum 115,200 bps): CICON Loader, CIMON-HMI, MODBUS RTU Slave / Type: RJ45 | |
Ethernet | Expanded: 10Base-T | - | ||
Event log | Power, Mode, Error | |||
Firmware Upgrade | Available | |||
Power | 5Vdc, 195mA | 5Vdc, 70mA | 5Vdc, 100mA | |
Weight (g) | 140g | 127g | 137g | |
Floating-point Arithmetic | - | |||
Capacity of Scan Program | 64K Steps | 16K Steps | ||
Device Memory
| X | 1,536 | 384 | |
Y | 1,536 | 384 | ||
M | 8,192 | |||
K | 2,048 | |||
L | 2,048 | |||
F | 2,048 | |||
T | 1,024 (select between 10 ms and 100 ms) | |||
C | 1,024 | |||
S | 100Card*100Step | |||
D | 10,000 Word | 5,000 Word | ||
Z | 1,024 Word | |||
Q | 512 Word | |||
R | 16 Word |
Item | Specification | ||||
CM1-CP3A | CM1-CP3B | CM1-CP3U | CM1-CP3P | ||
Program Control Method | Repetitive operation, Stored Program (ROM mode), Periodic operation | ||||
I/O Control Method | Scan synchronous batch processing system (I/O refresh), Indirect method, Direct method by instruction | ||||
Program Language | IL (Instruction List), LD (Ladder Diagram), FBD (Function Block Diagram), FBD Extension | ||||
Number of Instructions | Basic | 60 | |||
Application | 480 | ||||
Data Processing | LD | 0.2us / Step | |||
Program Memory | 512 Kbyte | ||||
Number of Program Blocks | Max 128, up to 65,530 steps per block (PID) | ||||
Number of I/O | 1,024 | ||||
Number of I/O Devices | Input: 32,768 points, Output: 32,768 points | ||||
Supporting Program | LD | Scan, Subroutine, Initialize (COLD), Initialize (HOT), Periodic interrupt | |||
Special Configuration | Initializing special card, PID control, Thermistor setting, Loadcell setting, I/O Input module filter setting | ||||
Communication | User protocol (Serial), User protocol (Ethernet), MODBUS TCP/RTU Master/Slave, Ethernet High-speed link, CIMON-NET Master/Slave, DNP3, Public network IP setting, Fieldbus | ||||
Periodic Interruption | Maximum 15, cycle setting (10–60,000 ms, Unit :10 ms), priority setting (0–14) | ||||
Base Expansion | Maximum 16 (10Base-T) | ||||
Max. Distance | Electricity (100 m) | ||||
Redundancy | - | ||||
Operation modes | LOCAL/Remote(RUN, STOP, PAUSE) | ||||
Restarting | Cold, Hot Restart | ||||
Self-Diagnosis | Monitoring delay of processing, problems of memory, I/O, battery, power error | ||||
Data Preservation Against Power Failure | K device and conservation (Latch) in M, L, T, C, S, D device | ||||
Watch Dog Timer (WDT) | Maximum 5000 ms (Unit: 10 ms) | ||||
Timer | On Delay, Off Delay, Addition, Monostable, Retriggerable Cycle: Either 10 or 100 ms TC (Current value)/TS (Setting value) | ||||
Counter | UP, DOWN, UP/DOWN, RING COUNTER, CC (Current value)/CS (Setting value) No limitation on number of points, Count range: -32,768–32,767 | ||||
PID | 32 Channels, Auto-Tuning | ||||
Communication Channels | USB |
- |
- | USB 2.0 B Type: For Loader Protocol |
- |
Serial | RS-232C (Maximum 38,400 bps): CICON Loader / Type: RJ11 | ||||
Ethernet | Expanded: 10Base-T | ||||
Event log | Power, Mode, Error | ||||
Firmware Upgrade | - | ||||
Power | 5Vdc, 240mA | ||||
Weight (g) | 135g | 135g | 153g | 139g | |
Floating-point Arithmetic | - | ||||
Capacity of Scan Program | 32K Steps | ||||
Device Memory
| X | 1,024 | |||
Y | 1,024 | ||||
M | 8,192 | ||||
K | 2,048 | ||||
L | 2,048 | ||||
F | 2,048 | ||||
T | 1,024 (select between 10 ms and 100 ms) | ||||
C | 1,024 | ||||
S | 100Card*100Step | ||||
D | 10,000 Word | ||||
Z | 1,024 Word | ||||
R | 16 Word |