Error Codes (Address "9")
Buffer Memory Address "9"
The error codes detected from a D/A module are stored in these addresses.
is from 1 to 4 for DA04I, DA04V and DA04VA and from 1 to 8 for DA08I, DA08V and DA08VA(The number means the channel.)
is from 1 to 3
If an error occurs, it will be kept till it is cleared or the power is off. If an error is not cleared after it occurs, a newly occurring error will be disregarded
Error code | Description |
1 | The case that a set digital input value is out of maximum range (16191, 8191) |
2 | The case that a set digital input value is out of minimum range (-192, -8192) |
40 | The case that an offset value is greater than a gain value |
41 | The case that both an offset and an gain are calibrated or two channels are set up at the same time |
42 | The case that a calibrated digital value is out of range when offset/gain is calibrated |
10 | Error in system (A/S required) |