Internal I/O Table - D/A Converters

Signal Direction (CPU <-D/A Module)

Signal Direction (CPU ->D/A Module)

Input

Signal Name

Output

Signal Name

X00

D/A module ready

Y00

Not use

X01

Not use

Y01

X02

Y02

X03

Y03

X04

Y04

X05

Y05

X06

Y06

X07

Y07

X08

Y08

X09

Y09

X0A

Flag indicating operation condition set up

Y0A

Requesting to set up operation condition

X0B

Flag indicating the channel switched

Y0B

Requesting to switch an channel

X0C

Flag indicating the set value modified

Y0C

Requesting to modify an set value

X0D

Flag indicating offset or gain calibration mode

Y0D

Requesting to calibrate offset or gain

X0E

Not use

Y0E

Assigning offset or gain calibration mode

X0F

Flag indicating an error in D/A module

Y0F

Requesting to clear an error

 

The numbers of I/O signal are the ones of the case that a D/A module is mounted on Slot 0 of a local base.