Buffer Memory - PLCS RTD

 

Address

Details

R/W

Address

Details

R/W

Hex

Dec

Hex

Dec

0H

0

RTD conversion Enable/Disable

R/W

1EH

30

Designate Average Process

R/W

1H

1

CH.1 Temp detection value(°C)

R

1FH

31

CH.1 Error code

R

2H

2

CH.2 Temp detection value(°C)

R

20H

32

CH.2 Error code

R

3H

3

CH.3 Temp detection value(°C)

R

21

33

CH.3 Error code

R

4H

4

CH.4 Temp detection value(°C)

R

22

34

CH.4 Error code

R

5H

5

CH.5 Temp detection value(°C)

R

23

35

CH.5 Error code

R

6H

6

CH.6 Temp detection value(°C)

R

24

36

CH.6 Error code

R

7H

7

CH.7 Temp detection value(°C)

R

25

37

CH.7 Error code

R

8H

8

CH.8 Temp detection value(°C)

R

26

38

CH.8 Error code

R

9H

9

Designate RTD type

R/W

27

39

Reserved

-

AH

10

Digital output setting 1

R/W

28

40

Requesting data for calibration

R/W

BH

11

CH.1 Temp detection value (°F)

R

29

41

CH.1 Max. temp input value

R/W

CH

12

CH.2 Temp detection value (°F)

R

2A

42

CH.2 Max. temp input value

R/W

DH

13

CH.3 Temp detection value (°F)

R

2B

43

CH.3 Max. temp input value

R/W

EH

14

CH.4 Temp detection value (°F)

R

2C

44

CH.4 Max. temp input value

R/W

FH

15

CH.5 Temp detection value (°F)

R

2D

45

CH.5 Max. temp input value

R/W

10H

16

CH.6 Temp detection value (°F)

R

2E

46

CH.6 Max. temp input value

R/W

11H

17

CH.7 Temp detection value (°F)

R

2F

47

CH.7 Max. temp input value

R/W

12H

18

CH.8 Temp detection value (°F)

R

30

48

CH.8 Max. temp input value

R/W

13H

19

Information for operation channel

R

31

49

Max. & Min. Scale setting data

R/W

14H

20

Designate RTD type

-

32

50

Max. and Min. set error

R

15H

21

CH.1 Digital conversion value

R

33

51

CH.1 Min. temp input value

R/W

16H

22

CH.2 Digital conversion value

R

34

52

CH.2 Min. temp input value

R/W

17H

23

CH.3 Digital conversion value

R

35

53

CH.3 Min. temp input value

R/W

18H

24

CH.4 Digital conversion value

R

36

54

CH.4 Min. temp input value

R/W

19H

25

CH.5 Digital conversion value

R

37

55

CH.5 Min. temp input value

R/W

1AH

26

CH.6 Digital conversion value

R

38

56

CH.6 Min. temp input value

R/W

1BH

27

CH.7 Digital conversion value

R

39

57

CH.7 Min. temp input value

R/W

1CH

28

CH.8 Digital conversion value

R

3A

58

CH.8 Min. temp input value

R/W

1DH

29

Digital output setting 2

R/W

3B-3E

59-62

CH1-CH4 average time/filter coefficient setting

R/W

 

** Buffer memory, which is a memory in module, stores digital values that are converted from input signal of RTD and records current operations for the module.

** Temperature conversion value or digital conversion value is stored to CPU memory using FROM command and they are used for programs.

** Each data is 2 byte of data.

** 4 channel modules do not use buffer memory of CH.5 ~ CH.8

** R/W indicates whether or not read/write is possible from PLC

R: read      W: write