User Controlled Loss in Weight Batch
This mode performs loss in weight batching but the comparator output is dependant only on the net weight data. This mode, while being more flexible than the automatic mode described in section "Automatic Loss in Weight Batch", is more difficult to implement. No compensation is performed in this mode.
After starting of this mode batch control, the batching signal (X6/7/8/9) is turned on until when the WGSTOP instruction or ‘Batch Stop’ command (code 3) with Y2/3/4/5 signal is issued by sequence program.
Dribble Flow Weight
offset 98, 144, 190, 236
If the net weight is below of this weight, the dribble flow gate signal is turned on.
Full Flow Weight
offset 100, 146, 192, 238
If the net weight is below of this weight, the full flow gate signal is turned on.
Over Weight
offset 102, 148, 194, 240
If the net weight is below of this weight, the over signal is turned on.
Under Weight
offset 104, 150, 196, 242
If the net weight is above of this weight, the under signal is turned on.
Max. Hopper Weight
Max. Hopper Weight offset 114, 160, 206, 252
If the gross weight is above of this weight, the ‘Hopper Gate’ bit (Bit 6) of control signal (offset 3, 18, 33, 48) is turned on.