Shared Memory - Loadcell

Data in this memory is shared with CPU through the system bus in base unit. All these data can be accessed by using the instruction (D)FROM and (D)TO instructions. Please refer to the CPU manual for more information of those instructions.

 

OFFSET

Description

Ch1

Ch2

Ch3

Ch4

0

15

30

45

Measured weight (low word)

 

R

1

16

31

46

Measured weight (high word)

 

R

2

17

32

47

Status flags (bit mapped)

 

R

3

18

33

48

Control outputs (bit mapped)

 

R

4

19

34

49

 

 

 

5

20

35

50

Gross weight (Zero applied, low word)

 

R

6

21

36

51

Gross weight (Zero applied, high word)

 

R

7

22

37

52

Command main code

 

R/W

8

23

38

53

Command sub code (low word)

 

R/W

9

24

39

54

Command sub code (high word)

 

R/W

10

25

40

55

Net weight (Tare applied, low word)

 

R

11

26

41

56

Net weight (Tare applied, high word)

 

R

12

27

42

57

AD data (raw value, low word)

 

R

13

28

43

58

AD data (raw value, high word)

 

R

14

29

44

59

Error Code

 

R

60

 

 

 

61

 

 

 

62

 

 

 

63

OS Version

 

R

64

 

 

 

65

 

 

 

66

 

 

 

67

 

 

 

68

 

 

 

69

 

 

 

70

116

162

208

Weighing Mode

 

R/W

71

117

163

209

Min. Scale Value

5

R/W

72

118

164

210

Max. weight (low word)

 

R/W

73

119

165

211

Max. weight (high word)

74

120

166

212

Zero range

1% of Max. weight

R/W

75

121

167

213

Motion detect range

1% of Max. weight

R/W

76

122

168

214

Motion detect time

100 mSec.

R/W

77

123

169

215

Auto zero range

1% of Max. weight

R/W

78

124

170

216

Auto zero time period

100 mSec.

R/W

79

125

171

217

Hysteresis range

1% of Max. weight

R/W

80

126

172

218

Hysteresis time limit

100 mSec.

R/W

81

127

173

219

Avr. Window size and Time

3 - 13

R/W

82

128

174

220

Digital filter constant

0 - 90%

R/W

83

129

175

221

 

 

 

84

130

176

222

 

 

 

85

131

177

223

 

 

 

86

132

178

224

 

 

 

87

133

179

225

 

 

 

88

134

180

226

 

 

 

89

135

181

227

 

 

 

90

136

182

228

 

 

 

91

137

183

229

 

 

 

92

138

184

230

 

 

 

93

139

185

231

 

 

 

94

140

186

232

 

 

 

95

141

187

233

 

 

 

96

142

188

234

Min. hopper weight (low word)

Max. Weight

R/W

97

143

189

235

Min. hopper weight (high word)

98

144

190

236

Dribble weight, high set point or set point #1 (low word)

Max. Weight

R/W

99

145

191

237

Dribble weight, high set point or set point #1 (high word)

100

146

192

238

Full flow weight, low set point or set point #2 (low word)

Max. Weight

R/W

101

147

193

239

Full flow weight, low set point or set point #2 (high word)

102

148

194

240

Over weight, High-High set point or set point #3 (low word)

Max. Weight

R/W

103

149

195

241

Over weight, High-High set point or set point #3 (high word)

104

150

196

242

Under weight, Low-Low set point or set point #4 (low word)

Max. Weight

R/W

105

151

197

243

Under weight, Low-Low set point or set point #4 (high word)

106

152

198

244

Comparator inhibit time after full flow start or set point #5 (low word)

100 mSec.

R/W

107

153

199

245

Comparator inhibit time after full flow stop or set point #5 (high word)

100 mSec.

R/W

108

154

200

246

Gate open time for compensation or set point #6 (low word)

100 mSec.

R/W

109

155

201

247

Gate closing time for compensation or set point #6 (high word)

100 mSec.

R/W

110

156

202

248

Target weight for compensation or set point #7 (low word)

Max. Weight

R/W

111

157

203

249

Target weight for compensation or set point #7 (high word)

112

158

204

250

Batch complete delay

100 mSec.

R/W

113

159

205

251

Batch limit time

100 mSec.

R/W

114

160

206

252

Max. hopper weight (low word)

Max. Weight

R/W

115

161

207

253

Max. hopper weight (high word)

254

 

 

 

255