Coincidence Output
This is used to output coincidence signal when a currently counted value is compared, being coincided with a set value. The coincidence output can be set up for 2 points each channel.
To output coincidence signal, enabling coincidence output (Y02(Y0A)) is to be on.
No. | Description |
1 | The set coincidence output value is stored in the set coincidence comparison value 1(ch1: 12H,13H,ch2:32H,33H ) in signed 32-bit binary. |
2 | When the currently counted value equals to the set coincidence output value, the counted value less is off and the counted value coincident is on. |
3 | If the requesting to reset coincidence signal is on, the counted value coincident is reset. If the counted value coincident is kept on, the next coincidence signal is not output. |
4 | If the counted value is greater than the set coincidence output value, the counted value greater is on. |