Digital output setting (Buffer memory address "10,29")
Select 0~16000,-8000~8000,-192~16191,-8192~8191 as digital output value. If -192 ~ 16191 or -8192 ~ 8191 is selected, the module displays minimum and maximum measured temperature for each thermocouple by 0~16000 or -8000~8000 and if input values exceed this range, it displays -192 ~ 16191, -8192 ~ 8191
Initial value is set to -192 ~ 16191.
In order to save set value to module, "requesting to save set value (Y02) must be ON/OFF.
Set value is stored in EEPROM and is operated by previous set value when power is turned ON/OFF.
Buffer memory address"10"
0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | CH.8 | CH.7 | CH.6 | CH.5 | CH.4 | CH.3 | CH.2 | CH.1 |
Buffer memory address"29"
0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | CH.8 | CH.7 | CH.6 | CH.5 | CH.4 | CH.3 | CH.2 | CH.1 |
Address 10 | Address 29 | Digital output value |
0 | 0 | -192 ~ 16191 |
0 | 1 | -8192 ~ 8191 |
1 | 0 | 0 ~ 16000 |
1 | 1 | -8000 ~ 8000 |