Detected Temperature Values °C ("1-8")

Detected Temperature Values °C ("1-8")

Buffer Memory Address "1~8"

The temperature values detected by TC conversion are indicated.
The values stored in a memory are actual temperature value * 10.

Range of the temperatures converted

TC Type

Rated Range of Measured Temperatures(oC)

Max. Indicated Range of Measured Temperatures(oC)

K

-200.0~1200.0

-250.0~1250.0

J

-200.0~800.0

-250.0~850.0

E

-200.0~600.0

-250.0~650.0

T

-200.0~400.0

-250.0~450.0

B

400.0~1800.0

350.0~1850.0

R

0.0~1750.0

-50.0~1800.0

S

0.0~1750.0

-50.0~1800.0

 

 

In case of the temperatures out of the rated range, they are outputted up to 50℃less than as the minimum and 50℃greater than the range as the maximum.