Installing and Wiring
Installation Environment
Conditions
Install in a waterproof and dustproof control panel.
Install at the place without continuous shock or vibration.
Keep out of the direct rays of the sun.
No dew caused by sudden temperature variation.
Keep the ambient temperature from 0 to 55 oC.
Works
In case of making bolthole or wiring, keep a PLC from dust and dregs.
Install at the place to operate easily.
Do not install together with high-voltage device and same panel.
The distance between ducts and modules is to be over 50 oC.
Ground at the place where the environment of noise is good.
Cautions
Do not drop or shock.
Do not separate a PCB from a case. That may be the reason of breakdown.
In case of wiring, take care that dregs come into the top of a module. If there are, remove them.
Mount or take out a module after turning off power.
Safety Precautions
Use separate cables for AC and outside input signals of a TC converter module to keep from the serge or the induced noise occurring from the AC.
Select the wire, considering ambient temperature, allowable current. AWG22(0.3 mm2) or more is recommended as the thickness of the wire.
Keep the wire out of heat-generating device, toxic substance and oil. They may cause breakdown or malfunction.
Make sure polarity before inputting analog value to a terminal block.
The wiring together with high-voltage line or power line may cause malfunction or breakdown.
Example of Wiring
Measured values are inputted to all the channels grouped as Terminal 7-8, 9-10, 11-12, 13-14.
|
Cable is to be used as conducting wires. Connect the shield part of a wire to FG terminal(No. 18) and ground it. Connect RJC to Terminal 1, 3 and 5. |