Installing and Wiring

Installation Environment

Conditions

  • Install in a waterproof and dustproof control panel.

  • Install at the place without continuous shock or vibration.

  • Keep out of the direct rays of the sun.

  • No dew caused by sudden temperature variation.

  • Keep the ambient temperature from 0 to 55 oC.

Works

  • In case of making bolthole or wiring, keep a PLC from dust and dregs.

  • Install at the place to operate easily.

  • Do not install together with high-voltage device and same panel.

  • The distance between ducts and modules is to be over 50 oC.

  • Ground at the place where the environment of noise is good.

 

Cautions

  • Do not drop or shock.

  • Do not separate a PCB from a case. That may be the reason of breakdown.

  • In case of wiring, take care that dregs come into the top of a module. If there are, remove them.

  • Mount or take out a module after turning off power.

 

Safety Precautions

  • Use separate cables for AC and outside input signals of a TC converter module to keep from the serge or the induced noise occurring from the AC.

  • Select the wire, considering ambient temperature, allowable current. AWG22(0.3 mm2) or more is recommended as the thickness of the wire.

  • Keep the wire out of heat-generating device, toxic substance and oil. They may cause breakdown or malfunction.

  • Make sure polarity before inputting analog value to a terminal block.

  • The wiring together with high-voltage line or power line may cause malfunction or breakdown.

 

Example of Wiring
Measured values are inputted to all the channels grouped as Terminal 7-8, 9-10, 11-12, 13-14.

 

 

 

image-20240325-054505.png

 

 

image-20240325-054518.png

Cable is to be used as conducting wires.

Connect the shield part of a wire to FG terminal(No. 18) and ground it. Connect RJC to Terminal 1, 3 and 5.