Setting up Channels

Setting up Channels

If you double-click the corresponding channel on the above window or click image-20240325-053322.png after selecting a channel, a Channel Features Setup dialog box will appear as follows.

 

image-20240325-053328.png
  • RTD Type : PT100 and JPT100 for RD04A / PT1000 for RD04B

  • Range of Digitally Converted Values : -192~16191, -8192~8191

  • Digital Filter : 0~70%

  • Average Operation : 1~255sec.

  •  

If you clickimage-20240325-053345.png , the icon is changed toimage-20240325-053348.png . Click the channel in the AD Module Setup dialog box to revise the set values for a corresponding channel.

 

Click 'OK' after the channel is set up.

 

image-20240325-053353.png

 

If you select all channels with the mouse as follows and image-20240325-053401.png , it will be available to set up all the channels.

 

Click image-20240325-053406.png to operate the RTD card with set values.
The message "Set values are recorded in module" is shown in the message bar.
After the set values are stored in EEPROM, even power is on/off, analog input values are converted with currently set channel values.

image-20240325-053412.png is used to read the currently set values in the AD card.

 

Status

If you click image-20240325-053421.png in the RTD Module Setup dialog box, the OS version, you can make sure the converted values and the Error Code for the RTD card and the scale of the converted temperature values can be set up.

 

 

If you select a channel and click image-20240325-053427.png , the following dialog box will appear.

 

 

The default digital value scale for -200oC ~ 600oC is 0(-8000) ~16000(8000). To revise the maximum and minimum temperature value, the Scale Setup is to be selected and the temperature when digital values are 0 and 16000 is be set up.

A set scale value is not stored in EEPROM. To apply this setup in case that power is on/off, write the part for applying the scale value in SCAN program.