Shared Memory - RTD Module

Address

Description

R/W

Address

Description

R/W

Hexa

Deci

Hexa

Deci

0H

0

Enabling/disabling to RTD-convert setup

R/W

1EH

30

Assigning Average Process

R/W

1H

1

Detected temp. value of CH.1(°C)

R

1FH

31

Error code value of CH.1

R

2H

2

Detected temp. value of CH.2(°C)

R

20H

32

Error code value of CH.2

R

3H

3

Detected temp. value of CH.3(°C)

R

21

33

Error code value of CH.3

R

4H

4

Detected temp. value of CH.4(°C)

R

22

34

Error code value of CH.4

R

5H

5

Detected temp. value of CH.5(°C)

R

23

35

Error code value of CH.5

R

6H

6

Detected temp. value of CH.6(°C)

R

24

36

Error code value of CH.6

R

7H

7

Detected temp. value of CH.7(°C)

R

25

37

Error code value of CH.7

R

8H

8

Detected temp. value of CH.8(°C)

R

26

38

Error code value of CH.8

R

9H

9

1)Assigning RTD type

R/W

27

39

Not use

-

AH

10

Not use

-

28

40

BH

11

Detected temp. value of CH.1 (°F)

R

29

41

Max. temp. input value of CH.1

R/W

CH

12

Detected temp. value of CH.2 (°F)

R

2A

42

Max. temp. input value of CH.2

R/W

DH

13

Detected temp. value of CH.3 (°F)

R

2B

43

Max. temp. input value of CH.3

R/W

EH

14

Detected temp. value of CH.4 (°F)

R

2C

44

Max. temp. input value of CH.4

R/W

FH

15

Detected temp. value of CH.5 (oF)

R

2D

45

Max. temp. input value of CH.5

R/W

10H

16

Detected temp. value of CH.6 (°F)

R

2E

46

Max. temp. input value of CH.6

R/W

11H

17

Detected temp. value of CH.7 (°F)

R

2F

47

Max. temp. input value of CH.7

R/W

12H

18

Detected temp. value of CH.8 (°F)

R

30

48

Max. temp. input value of CH.8

R/W

13H

19

Information on operating channels

R

31

49

Max./min. temp. setup data

R/W

14H

20

Not use

-

32

50

Error in max./min. setup

R

15H

21

Digitally converted value of CH.1

R

33

51

Min. temp. input value of CH.1

R/W

16H

22

Digitally converted value of CH.2

R

34

52

Min. temp. input value of CH.2

R/W

17H

23

Digitally converted value of CH.3

R

35

53

Min. temp. input value of CH.3

R/W

18H

24

Digitally converted value of CH.4

R

36

54

Min. temp. input value of CH.4

R/W

19H

25

Digitally converted value of CH.5

R

37

55

Min. temp. input value of CH.5

R/W

1AH

26

Digitally converted value of CH.6

R

38

56

Min. temp. input value of CH.6

R/W

1BH

27

Digitally converted value of CH.7

R

39

57

Min. temp. input value of CH.7

R/W

1CH

28

Digitally converted value of CH.8

R

3A

58

Min. temp. input value of CH.8

R/W

1DH

29

Digital output setup

R/W

3B-3E

59-62

Setting up average time /filter coefficient for CH1-CH4

R/W

 

Note 1) Only RD04A is for R/W and RD04B cannot be used.

  The buffer memory from CH.5 to CH.8 cannot be used for 4-channel module.
Each data is word type
R/W indicates whether reading/writing from a PLC is enabled. (R : Reading is enabled. W : Writing is enabled.)