Shared Memory - RTD Module
Address | Description | R/W | Address | Description | R/W | ||
Hexa | Deci | Hexa | Deci | ||||
0H | 0 | Enabling/disabling to RTD-convert setup | R/W | 1EH | 30 | Assigning Average Process | R/W |
1H | 1 | Detected temp. value of CH.1(°C) | R | 1FH | 31 | Error code value of CH.1 | R |
2H | 2 | Detected temp. value of CH.2(°C) | R | 20H | 32 | Error code value of CH.2 | R |
3H | 3 | Detected temp. value of CH.3(°C) | R | 21 | 33 | Error code value of CH.3 | R |
4H | 4 | Detected temp. value of CH.4(°C) | R | 22 | 34 | Error code value of CH.4 | R |
5H | 5 | Detected temp. value of CH.5(°C) | R | 23 | 35 | Error code value of CH.5 | R |
6H | 6 | Detected temp. value of CH.6(°C) | R | 24 | 36 | Error code value of CH.6 | R |
7H | 7 | Detected temp. value of CH.7(°C) | R | 25 | 37 | Error code value of CH.7 | R |
8H | 8 | Detected temp. value of CH.8(°C) | R | 26 | 38 | Error code value of CH.8 | R |
9H | 9 | 1)Assigning RTD type | R/W | 27 | 39 | Not use | - |
AH | 10 | Not use | - | 28 | 40 | ||
BH | 11 | Detected temp. value of CH.1 (°F) | R | 29 | 41 | Max. temp. input value of CH.1 | R/W |
CH | 12 | Detected temp. value of CH.2 (°F) | R | 2A | 42 | Max. temp. input value of CH.2 | R/W |
DH | 13 | Detected temp. value of CH.3 (°F) | R | 2B | 43 | Max. temp. input value of CH.3 | R/W |
EH | 14 | Detected temp. value of CH.4 (°F) | R | 2C | 44 | Max. temp. input value of CH.4 | R/W |
FH | 15 | Detected temp. value of CH.5 (oF) | R | 2D | 45 | Max. temp. input value of CH.5 | R/W |
10H | 16 | Detected temp. value of CH.6 (°F) | R | 2E | 46 | Max. temp. input value of CH.6 | R/W |
11H | 17 | Detected temp. value of CH.7 (°F) | R | 2F | 47 | Max. temp. input value of CH.7 | R/W |
12H | 18 | Detected temp. value of CH.8 (°F) | R | 30 | 48 | Max. temp. input value of CH.8 | R/W |
13H | 19 | Information on operating channels | R | 31 | 49 | Max./min. temp. setup data | R/W |
14H | 20 | Not use | - | 32 | 50 | Error in max./min. setup | R |
15H | 21 | Digitally converted value of CH.1 | R | 33 | 51 | Min. temp. input value of CH.1 | R/W |
16H | 22 | Digitally converted value of CH.2 | R | 34 | 52 | Min. temp. input value of CH.2 | R/W |
17H | 23 | Digitally converted value of CH.3 | R | 35 | 53 | Min. temp. input value of CH.3 | R/W |
18H | 24 | Digitally converted value of CH.4 | R | 36 | 54 | Min. temp. input value of CH.4 | R/W |
19H | 25 | Digitally converted value of CH.5 | R | 37 | 55 | Min. temp. input value of CH.5 | R/W |
1AH | 26 | Digitally converted value of CH.6 | R | 38 | 56 | Min. temp. input value of CH.6 | R/W |
1BH | 27 | Digitally converted value of CH.7 | R | 39 | 57 | Min. temp. input value of CH.7 | R/W |
1CH | 28 | Digitally converted value of CH.8 | R | 3A | 58 | Min. temp. input value of CH.8 | R/W |
1DH | 29 | Digital output setup | R/W | 3B-3E | 59-62 | Setting up average time /filter coefficient for CH1-CH4 | R/W |
Note 1) Only RD04A is for R/W and RD04B cannot be used.
The buffer memory from CH.5 to CH.8 cannot be used for 4-channel module.
Each data is word type
R/W indicates whether reading/writing from a PLC is enabled. (R : Reading is enabled. W : Writing is enabled.)