Output Signals

DeviceNO.

Signal Name

Description

Y02

Requesting to set up operation condition

This is set when the contents of enabling/disabling to A/D-convert, assigning average process, the average time and the average number of times when average process is assigned are available.

Refer to X02(Flag indicating operation condition set up) for set/reset timing.

Y03

Requesting to switch an channel

This is set when switching the channel for offset/gain calibration.

Refer to X03(Flag indicating channel switched) for set/reset timing

Y04

Requesting to calibrate offset or gain

This is set when the calibrated values of offsets/gains are registered to A/D module.

Refer to X04(Flag indicating offset/gain calibration mode) for set/reset timing.

Y05

Assigning offset or gain mode

This is set when assigning offset/gain calibration mode.

When it is reset, normal mode(A/D Conversion mode.

If offsets/gains are set up, this is to be reset.

Y0E

Requesting to reset maximum value and minimum value

If the request to reset maximum value and minimum value is set, the maximum value and minimum value stored in buffer memory will be cleared.

After this is set, this is to be reset.

Y0F

Requesting to clear an error

This is set to clear the error.