Buffer Memory - PLCS TC
Address | Details | R/W | Address | Details | R/W | ||
Hex. | Dec. | Hex. | Dec. | ||||
0H | 0 | TC conversion Enable/Disable | R/W | 23H | 35 |
Reserved |
- |
1H | 1 | CH.1 Temp detection value(oC) | R | 24H | 36 | ||
2H | 2 | CH.2 Temp detection value(oC) | R | 25H | 37 | ||
3H | 3 | CH.3 Temp detection value(oC) | R | 26H | 38 | ||
4H | 4 | CH.4 Temp detection value(oC) | R | 27H | 39 | ||
5H | 5 | Reserved | - | 28H | 40 | Request calibration | R/W |
6H | 6 | 29H | 41 | CH.1 Max. temp input value | R/W | ||
7H | 7 | 2AH | 42 | CH.2 Max. temp input value | R/W | ||
8H | 8 | 2BH | 43 | CH.3 Max. temp input value | R/W | ||
9H | 9 | CH.1~CH.4thermocouple type setting | R/W | 2CH | 44 | CH.4 Max. temp input value | R/W |
AH | 10 | Digital output setting 1 | R/W | 2DH | 45 | Reserved | - |
BH | 11 | CH.1 Temp detection value (oF) | R | 2EH | 46 | ||
CH | 12 | CH.2 Temp detection value (oF) | R | 2FH | 47 | ||
DH | 13 | CH.3 Temp detection value (oF) | R | 30H | 48 | ||
EH | 14 | CH.4 Temp detection value (oF) | R | 31H | 49 | Assigning temp. setting data | R/W |
FH | 15 | Reserved | - | 32H | 50 | Error in Temp. setting | R |
10H | 16 | 33H | 51 | CH.1 Min. temp input value | R/W | ||
11H | 17 | 34H | 52 | CH.2 Min. temp input value | R/W | ||
12H | 18 | 35H | 53 | CH.3 Min. temp input value | R/W | ||
13H | 19 | Information for operation Channel | R | 36H | 54 | CH.4 Min. temp input value | R/W |
14H | 20 | Assigning type setup data | R/W | 37H | 55 | Reserved | - |
15H | 21 | CH.1 Digital conversion value | R | 38H | 56 | ||
16H | 22 | CH.2 Digital conversion value | R | 39H | 57 | ||
17H | 23 | CH.3 Digital conversion value | R | 3AH | 58 | ||
18H | 24 | CH.4 Digital conversion value | R | 3B-3E | 59-62 | CH1-CH4 average time/filter coefficient setting | R/W |
19H | 25 | Reserved | - | 3FH | 63 | OS Version | R |
1AH | 26 | 40H | 64 | CH.1 Max. Temp. in changing | R/W | ||
1BH | 27 | 41H | 65 | CH.2 Max. Temp. in changing | R/W | ||
1CH | 28 | 42H | 66 | CH.3 Max. Temp. in changing | R/W | ||
1DH | 29 | Digital output setting 2 | R/W | 43H | 67 | CH.4 Max. Temp. in changing | R/W |
1EH | 30 | Assigning Average Process | R/W | 44H | 68 | Reserved | - |
1FH | 31 | CH.1 Error code | R | 45H | 69 | ||
20H | 32 | CH.2 Error code | R | 46H | 70 | ||
21H | 33 | CH.3 Error code | R | 47H | 71 | ||
22H | 34 | CH.4 Error code | R |
|
|
|
|
** Buffer memory, which is a memory in module, stores digital values that are converted from input signal of thermocouple and records current operations for the module
Temperature conversion value or digital conversion value is stored to CPU memory using FROM command and they are used for programs.
** Each data is 2 byte of data.
** 4 channel modules do not use buffer memory of CH.5 ~ CH.8
** R/W indicates whether or not read/write is possible from PLC
R : read W : write