Functions

TC conversion Enable / Disable
User can set TC conversion Enable or Disable for each input channel.
User can make conversion time short by setting Disable to unused channels.

Temperature detection value
It saves a converted Celsius and Fahrenheit into memory. (down to one decimal point X 10)
It converts the converted temperature into 0~16000, -192 ~ 16191, -8000 ~ 8000, -8192 ~ 8191.

Information for operation channels
Information for channels under normal temperature conversion is displayed for each channel.
If there is any disconnection error in TC conversion Enable channel, its bit becomes 0.
The bit for Disable channel is 0.

Disconnection detection function
It has a function to detect the disconnection of thermocouple and cable for each channel.
If disconnection is detected, TC module holds temperature value before disconnection without further conversion. In this case, error code is displayed while LED flickers every 0.2 second.

Digital output setting
User can select 0~16000, -192 ~ 16191, -8000 ~ 8000 and -8192 ~ 8191 as a range for saving digital output value to buffer memory.

Maximum/Minimum temperature setting
TC module converts allowable temperature for each thermocouple into digital value of 0(-8000)~16000(8000). This maximum and minimum value could be set by user. If a user inputs maximum and minimum value, TC module convert the minimum value into 0(-8000) and maximum value into 16000(8000).

Maximum Sample Temperature setting
This function is used to detects wrong temperature if previous sample temperature and current sample temperature are higher than a set temperature. User can set range of temperature from 3 to 1000.
If temperature is not updated under an environment with rapidly changing temperature, user should set higher temperature than current set value.