Setting Raw Value digital output - PLCS AD/DA

This sets range of digital conversion to be outputted as Raw Value

This is set to 2 bit per channel. Refer to following table

 

[Bit Mapping : 16 bits]

MSB                                                                         LSB

0

0

0

0

0

0

0

0

CH4

CH3

CH2

CH1

 

[16 Bit Resolution]

Code

Normal input range

Full Range

00 (0)

-32000 ~ +32000

-32767 ~ +32768

01 (1)

-32000 ~ +32000

-32000 ~ +32000

10 (2)

500 ~ 64500

0 ~ 65000

11 (3)

0 ~ 64000

0 ~ 64000

 

[14 Bit Resolution]

Code

Normal input range

Full Range

00 (0)

-8000 ~ +8000

-8192 ~ +8191

01 (1)

-8000 ~ +8000

-8000 ~ +8000

10 (2)

0 ~ 16000

-192 ~ 16191

11 (3)

0 ~ 16000

0 ~ 16000

 

Full Range : It is range for conversion for input signal which is off the normal range.