Setting Raw Value digital output - PLCS AD/DA
This sets range of digital conversion to be outputted as Raw Value
This is set to 2 bit per channel. Refer to following table
[Bit Mapping : 16 bits]
MSB LSB
0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | CH4 | CH3 | CH2 | CH1 |
[16 Bit Resolution]
Code | Normal input range | Full Range |
00 (0) | -32000 ~ +32000 | -32767 ~ +32768 |
01 (1) | -32000 ~ +32000 | -32000 ~ +32000 |
10 (2) | 500 ~ 64500 | 0 ~ 65000 |
11 (3) | 0 ~ 64000 | 0 ~ 64000 |
[14 Bit Resolution]
Code | Normal input range | Full Range |
00 (0) | -8000 ~ +8000 | -8192 ~ +8191 |
01 (1) | -8000 ~ +8000 | -8000 ~ +8000 |
10 (2) | 0 ~ 16000 | -192 ~ 16191 |
11 (3) | 0 ~ 16000 | 0 ~ 16000 |
Full Range : It is range for conversion for input signal which is off the normal range.