Module Specifications - TC Module
| Specification | |
Available Thermocouple | Type K, J, E, T, B, R, S ,N | |
Digital Output | · Digitally Converted Value : 0 ~ 16000(-8000~8000), · Converted Temperature Value:(Range of Measured Temp.X10) | |
Range of Temperature |
| |
RJC | Automatic | |
Detecting the breaking of wires | By channels | |
Accuracy | [(Full Scale)x0.3%+1oC(RJC Error)] | |
Max. converted Rate | 50ms / channel | |
No. of Input Channels | 4 channels / module | |
Type of Insulation | · Between input terminal and PLC : Photo Coupler Insulation · Between output channels : No Insulation | |
Connection Terminal | 18-point Terminal | |
Current Consumtion (mA) | +5V | 60 |
+15V | 30 | |
-15V | 10 |