Module Specifications - TC Module

 

 

Specification

Available Thermocouple

Type K, J, E, T, B, R, S ,N

Digital Output

· Digitally Converted Value : 0 ~ 16000(-8000~8000),

· Converted Temperature Value:(Range of Measured Temp.X10)

Range of Temperature

 

image-20240325-054252.png

RJC

Automatic

Detecting the breaking of wires

By channels

Accuracy

[(Full Scale)x0.3%+1oC(RJC Error)]

Max. converted Rate

50ms / channel

No. of Input Channels

4 channels / module

Type of Insulation

· Between input terminal and PLC : Photo Coupler Insulation

· Between output channels : No Insulation

Connection Terminal

18-point Terminal

Current Consumtion (mA)

+5V

60

+15V

30

-15V

10