Digital Output Setup ("29")

Buffer Memory Address "29"

This is used to select whether the range of digital output values is from 0 to 16000 or from –8000 to 8000.

If 0 is set up, the range is from 0 to 16000. If 1, it is from –8000 to 8000.

To make digital output setup available, requesting to set up an operation condition (Y02) is to be set and reset.

The range from 0 to 16000 is set up as default value.

As a set value is stored in EEPROM, the RTD module is operated as previously set value even though power is on and off.