Shared Memory - PLCS DA
Address | Details | Default | R/W | |
Hex. | Dec. | |||
00H | 0 | DA conversion Enable/Disable setup | 0 | R/W |
01H | 1 | CH.1 Digital output value | 0 | R/W |
02H | 2 | CH.2 Digital output value | 0 | R/W |
03H | 3 | CH.3 Digital output value | 0 | R/W |
04H | 4 | CH.4 Digital output value | 0 | R/W |
05H | 5 | CH.1 Range of digital value | 0 | R/W |
06H | 6 | CH.2 Range of digital value | 0 | R/W |
07H | 7 | CH.3 Range of digital value | 0 | R/W |
08H | 8 | CH.4 Range of digital value | 0 | R/W |
09H | 9 | CH.1 Channel Hold / Clear | 0 | R/W |
0AH | 10 | CH.2 Channel Hold / Clear | 0 | R/W |
0BH | 11 | CH.3 Channel Hold / Clear | 0 | R/W |
0CH | 12 | CH.4 Channel Hold / Clear | 0 | R/W |
0DH | 13 | CH.1 Setup output range for channel (DIP S/W setting needed) | 0 | R/W |
0EH | 14 | CH.2 Setup output range for channel (DIP S/W setting needed) | 0 | R/W |
0FH | 15 | CH.3 Setup output range for channel (DIP S/W setting needed) | 0 | R/W |
10H | 16 | CH.4 Setup output range for channel (DIP S/W setting needed) | 0 | R/W |
11H | 17 | CH.1 Status | 0 | R |
12H | 18 | CH.2 Status | 0 | R |
13H | 19 | CH.3 Status | 0 | R |
14H | 20 | CH.4 Status | 0 | R |
15H | 21 | Error Code | 0 | R |
16H | 22 | OS Version | 0 | R |
17H | 23 | Enable DA output | 0 | R/W |
** Each data is Word type.
** R/W is to denote Read/Write if available from PLC program.
R: Read W: Write