Functions of Analog Output Module

  • D/A conversion Enable/Disable settings
    It is used to set D/A conversion Enable/Disable for each output channel.
    If disused channel is set as Disable, it outputs offset value (4mA or –10V)
    The conversion speed is at constant regardless of conversion Enable/Disable settings.

  • Analog output Clear/Hold settings
    It is used to hold or clear out analog value when PLC status is Stop mode or Error.
    (User can select it in "Stop mode output")

  • Offset/Gain settings
    When digital input value is 0~16000, -8000~8000, analog output can be calibrated to 4~20mA or –10~10V.

  • Digital output settings
    When digital input value is saved to Buffer memory, the range 0~16000 or –8000~8000 can be selected.

  • D/A Channel output Enable/Disable settings (Set output)
    It is used to select output D/A conversion value or offset value to each output channel.
    The conversion speed is at constant regardless of Output Enable/Disable settings.

    • Although D/A conversion is enabled but if Channel output is Disabled, D/A conversion value does not output but output only Offset value (4mA or -10V). As D/A conversion Enable/Disable settings are not saved, select Output Enable through using "TO" command at the first scan in order to use channel.