AD08I

 

image-20240325-025215.png

 

No.

Range of Analog Input

Offset

Gain

Digital Output Value

Max. Resolution

1

0 ~ 20mA

0mA

20mA

0 ~ 16000(-8000~8000)

1.25mA

2

4 ~ 20mA

4mA

20mA

1mA

In case that the analog inputs corresponding to the digital output values out of the range come, the maximum and the minimum of the digital output values are fixed as –192 and 16191(-8192 & 8191).