User Communication (SND, RCV)
Exclusive Commands for Computer Communication,
This is used when the communication frame defined in a user program is used to send and receive data in a program.
SND
This is used to send data as much as the length of the data requested from a computer link module.
CMD | Usable Device | |||||||||||
M | X | Y | K | L | F | T | C | S | D | @D | Integer | |
Base |
|
|
|
|
|
|
|
|
|
|
| O |
Chan |
|
|
|
|
|
|
|
|
|
|
| O |
Slot |
|
|
|
|
|
|
|
|
|
|
| O |
Addr | O | O | O | O | O | O | O | O | O | O | O |
|
Leng |
|
|
|
|
|
|
|
|
|
|
| O |
Result | O | O | O | O | O |
| O | O | O | O | O |
|
COMMAND | Description |
Base-Chan-Slot | Base: The number of the base where a computer link module is mounted is indicated. In case of expansion base, the number (1~16) of a corresponding base is indicated. In case of local one, the number is ‘0’.
Channel Mode: Ch 1(RS232:0) and Ch 2(RS422:1).
Slot No.: The number of the slot where a computer link module is mounted [Ex.] In case of local base, Slot 2, Channel 1(RS232) -> h0002 : RS-232C [Ex.] In case of expansion base (1), Slot 1, Channel 2(RS422) -> h0111 : RS-422 |
Addr | Address of the data sent |
Leng | Length of the data sent (BYTE), Decimal figure, Max. 500BYTE |
Result | The address where the result of sending is noticed is assigned. (X,Y,M,L,K,T,C,D,@D,Z)
Result Format : · Bit 0 : When sending completed, 1Scan ON. When failed, always ON. · Bit 1 : When sending failed, always ON. · Bit 2-7 : OFF · Bit 8-F : Error Code (0=No Error) |
FORMAT
RCV
This is used to store data as much as the length of the data requested from a computer link module.
CMD | Usable Device | |||||||||||
M | X | Y | K | L | F | T | C | S | D | @D | Integer | |
Base |
|
|
|
|
|
|
|
|
|
|
| O |
ChNo |
|
|
|
|
|
|
|
|
|
|
| O |
Slot |
|
|
|
|
|
|
|
|
|
|
| O |
Addr | O | O | O | O | O | O | O | O | O | O | O |
|
Leng |
|
|
|
|
|
|
|
|
|
|
| O |
Result | O | O | O | O | O |
| O | O | O | O | O |
|
COMMAND | Description |
Base-Chan-Slot | Base: The number of the base where a computer link module is mounted is indicated. In case of expansion base, the number (1~16) of a corresponding base is indicated. In case of local one, the number is ‘0’.
Channel Mode: Ch 1(RS232:0) and Ch 2(RS422:1).
Slot No.: The number of the slot where a computer link module is mounted [Ex.] In case of local base, Slot 0, Channel 1(RS232)-> h0000 : RS-232C [Ex.] In case of expansion base (1), Slot 4, Channel 2(RS422)-> h0114 : RS-422 |
Addr | Address where data are received and stored |
Leng | Length of the data received (BYTE), Decimal figure, Max. 500BYTE |
Result | The address where the result of receiving is noticed is assigned. (X,Y,M,L,K,T,C,D,@D,Z)
Result Format : · Bit 0 : When receiving completed, 1Scan ON. When failed, always ON · Bit 1 : When receiving failed, always ON · Bit 2-7 : OFF · Bit 8-F : Error Code (0=No Error) |
FORMAT