1.2.2 Advanced settings
Tag Settings - Advanced |
1. Digital Tag
Â
Initial Value
If it is a real tag, the 'Write initial value to I/O device' option should be checked. If it is a virtual tag, it is applied regardless of the initial value device write option.Invert Value from I/O Device
Displays the value read from the device inverted. The actual data value will be displayed as OFF when it is ON and ON when it is OFF.OFF / ON Label
Defines the string to display when OFF or ON. Tag variables can be used in tag value objects to display on the screen.
Â
In this case, instead of 0's and 1's, we will display the string defined by the OFF/ON label.
2. Analog Tag
Initial Value
If this is a physical tag, the "Write Initial Value Device" option must be checked. If it is a virtual tag, the Write Initial Value Device option will be applied regardless.
Â
Deadband
This does not apply to virtual tags; it only applies to real tags and will only cause the tag's value to change if the value exceeds the value set as Deadband.
Â
※Application examples
If the actual value of the device for the current tag is 0 and the Deadband is set to 100, the actual value of the device from 0 to 100 will be displayed as 0 in CIMON, and if it becomes 101, it will be displayed as 101 in CIMON. |
Â
Engineering Data
If the tag is virtual, it is scaled to the maximum and minimum values of the tag as seen in CIMON. If it is a real tag, it is combined with the real data and used to scale proportionally.
Raw Data
If it is a virtual tag, it will not be applied. If it is a real tag, it will be combined with internal data and scaled proportionally.
※ Scaling with Engineering Data / Raw Data
Â
Tag Value = Device’s Actual Value x Engineering Data(Max - Min) / Raw Data (Max – Min) |
Â
Scale
An arithmetic expression is used to transform the data values from the device so that they can be monitored.
The following formulas are applied
Tag Value = Device’s Actual Value * Scale + offset |
Generate data for reports
This will generate data for report output. This must be checked in order to use the report-related function Tlogval().
Resetting accumulated values manually
Select if this accumulated tag is a tag that will be manually reset.
3. String Tag
Â
String Length
Sets the maximum length of the string.
Initial Value
Applies if the tag is virtual, and specifies the value that is initially displayed when CIMON starts.
Â