Thermistor setting Program

CM1-TH08A is used to measure the temperature by calibrating thermistor resister. Please refer to the manual of thermistor module”

Registering NEW Program

Select [ File – New program..], and input " Program Name"

 

image-20240329-081054.png

Select the [OK] button.

 

Writing a thermistor program

Example of writing a thermistor program

After Registering NEW program, below the box appear.

 

image-20240329-081116.png

Register " BASE" and " Slot " which set thermistor.

 

 

Setting Channels

Setting Tab: This is used to set "Status", " Digital Range" ,"Digital Filter", "Average OP" and "Device"

 

Drag a mouse, you can select many channels.
If you want only one channel, select a channel by clicking a mouse.
By using a ctrl-Key, you can select channels what you want.

 

Select "EDIT", below the box appear

 

 

Select or unselect the blank, "enable"

 

 

Check the blank "Enable", you can change values.

Digital Range : it is used to convert the max/min temperature to digital value by a temperature converting table.

 

 

Digital Filter : It is used to set up in case of hunting by outside noise for converted temperature.
It is restricted converted ranges before storing converted temperature.

 

 

Range of set value : 0 ~ 70 %

Example : Values which stored the buffer memory is present values by adjusting Digital Filter.
Present Value = Present value + (formal value – present value) * Digital Filter(%) / 100

Average : It is used to set up calibrating value for average times

 

 

Range of set value : 0 ~ 255 sec.

Device : It is used to store converted temperature in CPU memory.

 

 

Enable domain: X, Y, M, L, K, D
Type of stored data: °F, ℃, digital value

Example: If you set like above the box, you can store ℃ value in D100.

Table Tab : It is used to input the temperature, and resistance of a thermistor

 

Please register the values refer to temperature-resistance table by provided manual from thermistor cooperation.

Center P. temperature = Max. Temperature – (Max. Temperature – Min. Temperature) / 2

In case of inputting the temperature-resistance table incorrectly, converted temperature value is out of range (0.3%)

Example : Max. temperature = 100℃, Min. temperature = -20℃

100 – (100 - (- 20) / 2 = 100 – 60 = 40℃

Register temperature values (Max. = 100℃, Center = 40℃, Min. = -20℃), and then Input resistance values of each temperature

 

 

Resistance value is except for a decimal point

Cable resistance: It is used to settle a resistance of cable resistance.