User Memory - PLCS Ethernet

Address

Details

Note

R/W

Dec.

0

Status Code (0=Normal, Others=Error Code)

 

R

3

CPU Response Error

 

 

4,5

IP Address (Upper, Lower)

 

R/W

6,7

Net Mask (Upper, Lower)

 

R/W

8

PLC Link Station No.

 

R

9

PLC Link Connection

15 - 0

R

10

PLC Link Connection

31 - 16

R

11

PLC Link Connection

47 – 32

R

12

PLC Link Connection

63 – 48

R

13,14

Latest HMI Service IP Address (Upper, Lower)

 

R

15

Latest HMI Service Port

 

R

16,17

Latest Loader Service Address (Upper, Lower)

 

R

18

Latest Loader Service Port

 

R

19

TCP ModBus Unit ID

 

R/W

20,21

Destination IP Address (Upper, Lower)

 

R

22

Destination Port

 

R

23,24

Source IP Address (Upper, Lower)

 

R

25

Source Port

 

R

26,27

Gateway (Upper, Lower)

 

R/W

 

 

 

63

OS Version

 

R

 

 

 

90

[User Protocol] Change Dynamic IP, Port

1 = Set IP Address

2 = Set Port

3 = Reset Host

R/W

91

[User Protocol] New Host Number

 

R/W

92

[User Protocol] First byte of the IP address or Port

111 of

111.222.333.444

R/W

93

[User Protocol] Second byte of the IP address

222 of

111.222.333.444

R/W

94

[User Protocol] Third byte of the IP address

333 of

111.222.333.444

R/W

95

[User Protocol] Fourth byte of the IP address

444 of

111.222.333.444

R/W

 

 

 

108

Comm. Monitor Status

0 ~ 7bit

R

109

Comm. Monitor Timeout (msec)

0 = Disable

500 ~ 60000

R/W

110,111

Comm. Monitor IP Address_0 (Upper, Lower)

 

R/W

 

 

 

124,125

Comm. Monitor IP Address_7 (Upper, Lower)

 

 

126

PLC Link Enable/Disable

 

R

127

PLC Link Status

 

R/W

128,129

IP Address of PLC Link Station No.0 (Upper, Lower)

 

R/W

 

 

 

254,255

IP Address of PLC Link Station No.63 (Upper, Lower)

 

R/W